SECTION IB-2A-220

INSTRUCTIONS FOR OPERATION DEAD-FRONT FUSE PANEL

TYPE PSE PAD-MOUNTED SWITCHGEAR 

SEPT 2022

PAGE 1

DEAD-FRONT FUSE PANEL

TYPE PSE PAD-MOUNTED SWITCHGEAR

15kV • 25kV

INSTRUCTIONS FOR OPERATION

1.   Install and secure a feed-thru stand-off bushing on the parking stand. The feed-thru device 

must be oriented so that it will not interfere with the operation of the hinged fuse-panel.

2.   If switching of energized elbows is permitted, proceed to Step 3 below. If switching of energized 

elbows is NOT permitted, test the circuit in accordance with the user’s standard operating 

practices and using equipment rated for the voltage involved to verify that the circuit is de-

energized.

3.  After verifying the applicable de-energized/energized condition of the elbow to be 

switched and following the elbow manufacturer’s operating instructions:  

  a.  Pull the elbow off the loadbreak insert and properly re-position it onto the feed-thru 

stand-off bushing. Make certain that the connected high-voltage cable is retained within 

the cable guide and moves so it is clear of the fuse panel, which must be free to pivot 90°.

 

b.   Using equipment rated for the voltage involved, test the re-positioned elbow for voltage 

through the uncovered loadbreak insert of the feed-thru.  

 

c.   After verifying that voltage is not present, properly install the grounding elbow in accordance 

with the grounding-elbow manufacturer’s instructions and the user’s standard operating 

practices, first clamping the ground connector to the ground buss and then installing the 

grounding elbow on the unoccupied loadbreak insert of the feed-thru.

  d.  Ensure that the cables, feed-thru devices, and elbows are not located where they would 

interfere with the operation of the fuse panel. Reposition as needed.

4.  With the hook of the shot-gun clamp stick secured to the interlock latch grip rod on the fuse-

panel (see Figure 1), raise the latch to the horizontal position and verify that the interlock latch 

locking rod is free of the notched latch brackets at the sides. See Figure 2.

Figure 1.  Interlock lever being raised 

to unlocked position (or lowered to 

locked position).

Figure 2.  Fuse mounting being lowered 

to access fuse (or raised to reinstall 

fuse).

NOTICE

Load-break inserts and loadbreak elbows used in combination with the Federal Pacific Dead-

Front PSE Pad-Mounted Switchgear are rated for load switching of currents to 200 amperes 

continuous.  Consequently, the 200-amp elbow may be pulled, in accordance with the elbow 

manufacturer’s instructions, to perform the load-switching function. Pulling the energized elbow 

interrupts the load current connected to the associated circuit. The elbow is then parked on 

a standoff bushing. Then, only after the elbow has been parked, the fuse panel can be rotated 

(pivoted) to expose the fuse that is to be removed. With the elbow removed, rotation of the fuse 

panel does not involve any load switching. The removal of the fuse from the fuse panel can be 

accomplished using the shotgun stick or, since the fuse once exposed is completely and visibly 

isolated from voltage at both ends, and if standard operating practices permit, the fuse can be 

removed by hand when wearing gloves insulated for the voltage involved.

© 2021 Electro-Mechanical, LLC

WARNING

These instructions are provided as a quick reference and are not intended as a substitute for the detailed instructions contained in Instruc-

tion Bulletin IB-2A-210. These instructions are intended to be performed by thoroughly trained, qualified personnel that are familiar with 

the equipment, the operation and maintenance of the equipment and the hazards involved in performing the functions described in this 

document and Instruction Bulletin IB-2A-210.

DANGER

Before energizing the switchgear, remove all yellow and red shipping caps on bushings and bushing wells, and replace them with a suitable 

system of insulated separable connectors (elbows), insulating protective covers, or plugs, as appropriate.

Failure to remove the shipping caps may result in flashover, equipment damage, serious personal injury, or death.