FEDERAL PACIFIC AUTO-JET AJS Скачать руководство пользователя страница 1

1075 Old Airport Road • Bristol, VA 24201   Phone (276) 669-4084 • FAX (276) 645-8206 • www.federalpacific.com • ISO9001:2015

SECTION IB-3A-310A

INSPECTION & MAINTENANCE RECOMMENDATIONS

JUNE 2021

PAGE 1

TYPE AJS — AUTO-JET

®

 SWITCHES

15kV • 25kV • 38kV

INSPECTION & MAINTENANCE RECOMMENDATIONS

The procedures required for operation of the Federal Pacific Auto-

jet

®

  Load-Interrupter  Switches.  The  inspection  and  maintenance 

recommendations  covered  in  this  bulletin  are  expected  to  be 

performed in conjunction with a review of IB-3A-310. This bulletin 

does not cover all the detailed and specific operational procedures 

and checks. In addition, these instructions are not intended as a 

substitute for the user’s standard operating practices and procedures. 

A copy of Instruction Bulletin Section IB-3A-310 can be printed from 

the internet at www.federalpacific.com.

When cleaning components, 

NEVER

 use any industrial strength 

cleaners.  

NEVER

 apply lubricants to the probe contact or the 

tulip contact which are the interrupting contacts. 

NEVER

 use any 

solvent-based or flammable products on any components in the 

pad-mounted switchgear. Solvents and flammable products can 

attack non-metallic components of the equipment and reduce 

electrical and mechanical properties.

Maintenance

Federal  Pacific  switchgear  does  not  require  routine  mechanical 

or  electrical  maintenance.  However,  the  following  are  some 

recommendations for enhancing continued service of the equipment.

Before Opening the Switchgear

The following inspection and maintenance procedures must be 

performed with the unit completely de-energized and isolated from 

voltage. Any attempt to perform the inspection and maintenance 

with the unit energized may result in electrical arc flash that can 

cause equipment damage, personal injury or death.

WARNING

DANGER

© 2021 Electro-Mechanical Corporation

Qualified Persons

The equipment covered by this publication must be selected for a specific 

application and it must be operated and maintained by 

Qualified Persons

 

who are thoroughly trained  and knowledgeable in the installation, operation, 

and maintenance of underground power distribution equipment along with 

the associated hazards that may be involved. This publication is written only 

for such qualified persons and is not intended to be a substitute for adequate 

training and experience in safety procedures for this type of equipment. 

Proper installation is the responsibility of the operating and construction 

personnel and the utility performing and authorizing the work. Completion 

of these instructions implies no further warranty by the manufacturer.

Qualified Person

 is defined in the National Electrical Code (NEC/NFPA-

70) as:

One who has skills and knowledge related to the construction and operation 

of the electrical equipment and installations and has received safety training 

to recognize and avoid the hazards involved.

The  specific  electrical  safety  training  requirements  to  be  considered  a 

qualified person are detailed in 

NFPA-70E, Article 110.1(D), Employee 

Training

.  Some of the requirements from the 2012 edition are shown below.  

For the specific detailed training requirements for a Qualified Person make 

certain to refer to the most recent applicable edition.

These training requirements would include, but are not limited, to the 

following key points:

• The skills and techniques necessary to distinguish exposed energized 

parts from other parts of electrical equipment.

• The skills and techniques necessary to determine the proper approach 

distances corresponding to the voltages to which the qualified person will 

be exposed.

• The proper use of the special precautionary techniques, personal protective 

equipment, insulating and shielding materials, and insulated tools for 

working on or near exposed energized parts of electrical equipment.

• Tasks performed less often than once per year have additional training 

requirements.

These instructions are intended only for such qualified persons. They are not 

intended to be a substitute for adequate training and experience in safety 

procedures for this type of equipment. Additionally, the recommendations 

in this instruction bulletin are not intended to supersede or to take the place 

of established utility safety guidelines and established practices. If there 

is any question, consult with your foreman or supervisor, as appropriate.
Please refer to OSHA 29 CFR 1910.399 and NFPA 70E Articles 100 and 110.

WARNING

 

Содержание AUTO-JET AJS

Страница 1: ...operation andmaintenanceofundergroundpowerdistributionequipmentalongwith theassociatedhazardsthatmaybeinvolved Thispublicationiswrittenonly forsuchqualifiedpersonsandisnotintendedtobeasubstituteforadequate training and experience in safety procedures for this type of equipment Proper installation is the responsibility of the operating and construction personnelandtheutilityperformingandauthorizing...

Страница 2: ...e short circuit rating of the equipment 4 Switch Operation Do not put any lubricant on switch probe or puffer contacts Refer to Section 6 Lubrication Check switch for proper operation refer to Instruction Bulletin IB 3A 310 If the switch is closed on a short circuit within the fault closing rating and the short circuit is cleared by circuit breakersorfuses theswitchwillnotsustaindamagewhichwould r...

Страница 3: ...eldment at right removed from fuse mounting LUBRICATE ONLY 1 On the switch main contact stab See Figure 1 2 On the contact interface at the fuse mounting stationary main contact See Figure 2 3 OntheforwardcontactthatengagesthefusecontactrodandonthefusehingecontactsthatengagethefusecontactferruleThecontact rod and fuse ferrule on the fuse assembly Refer to fuse manufacturer s instructions 4 DO NOT ...

Страница 4: ...INTENANCE RECOMMENDATIONS JUNE 2021 PAGE 4 Every effort is made to ensure that customers receive an up to date instruction manual on the use of Federal Pacific products however from time to time modifications to our products may without notice make the information contained herein subject to alteration 2021 Electro Mechanical Corporation Notes ...

Отзывы: