Instruction Manual
Digital Input/Output Interface Card "OPC-DIO"
Thank you for purchasing the digital input/output interface card "OPC-DIO". By installing digital input/output interface card
"OPC-DIO" on the FRENIC series, frequency settings can be specified with binary codes and BCD codes, output frequency
and so on can be monitored with binary codes, and general-purpose input/output terminals can be expanded.
1. Applicable Inverters
Table 1 shows applicable inverter series.
Table 1 Applicable Inverter and ROM Version
Series Inverter
type
Inverter capacity
ROM version
FRENIC-Ace FRN
□□□
E2
□
-
□□□
Full capacity
0300 or later
2. Product Check
Check the following items.
(1) Ensure that the package contains the DIO
interface card and 2 screws (M3 x 8).
(2) Ensure that no damage such as abnormalities,
dents, or bending has occurred to the parts on the
DIO interface card during transport.
(3) Ensure that the "OPC-DIO" model name is
stamped on the top of the DIO interface card. (Fig.
2-1)
If you suspect the product is not working properly or if
you have any questions about your product, contact the
shop where you bought the product or your local Fuji
branch office.
Fig. 2-1 Front of Card
Fig. 2-2 Back of Card
Screw attachment hole
Removal knob
SW11
Model
CN1
Screw attachment hole
4. Electrical Specifications
3. Basic Connection Drawing
Table 4-1 Electrical Specifications List
FRENIC-Series
M1
L1/R
L2/S
L3/T
I13
I12
I11
I10
I9
I8
I7
I6
I5
I4
I3
I2
I1
CM
U
V
W
(LSB)
SOURCE
SINK
SW11
O8
O7
O6
O5
O4
O3
O2
O1
M2
(LSB)
(MSB)
Ry
Ry
Ry
Ry
Ry
Ry
Ry
Ry
(MSB)
(SEL)
Specification
Terminal
symbol
Item
Min. Max.
ON level
0 V
2 V
Operating
voltage
(SINK)
OFF level
22 V
27 V
ON level
22 V
27 V
Operating
voltage
(SOURCE)
OFF level
0 V
2 V
Operating current at ON
I1 - I13
2.5mA 5mA
(when input voltage 0 V)
Allowable leakage current at
OFF
-
0.5mA
ON level
-
2 V
Operating
voltage
OFF level
-
27 V
Fig. 3-1 Basic Connection Drawing
Before starting installation and wiring, turn OFF the power and wait at least ten minutes. Mace sure that the LED monitor
and charging lamp are turned OFF. Further, make sure, using a multimeter or a similar instrument, that the DC link bus
voltage between the terminals P(+) and N(-) has dropped to the safe level (+25 VDC or below)
Otherwise, electric shock could occur.
Maximum current at ON
-
50mA
O1 - O8
Leakage current at OFF
-
0.1mA
- 1 -