- 9 -
For DN15-DN80, the meter can be made with threading to connect.
The above table is used for rated pressure of 1.6MPa. If the rated pressure is more than 1.6MPa, please
contact us for special order.
4. Wiring
4.1 Preparation of wiring
You should read and connection method of supporting the use of thermal mass flowmeter
or other unit instrument system and requires careful - before connection;
The external cable recommended two core shielded cable and cable connection and
good sealing;
The explosion-proof products should be selected in accordance with the relevant
standard of BenAn instrument cable and make sure that the cable parameters meet the
explosion-proof instrument system requirements;
Working voltage range of DC18~30V. When the voltage is higher than DC30V, the
instrument will be damaged, and measures should be taken to prevent the supply voltage
from above 30V;
To the 24V DC power supply thermal mass flowmeter shall meet the requirements of
IEC-1010-1 or equivalent standard SELV safety extra low voltage;
Before the connection with the voltmeter to measure the power supply voltage, the
voltage is DC24V;