- 33 -
Appendix 1 Modbus register address table
Floating point data arrangement is F2-F1-F4-F3 (F4-F3-F2-F1 High to low)
register address
Register name
Register
number
data type
data format
4x0001-4x0002
Flow
2
float
IEEE754
TXD
01 03 00 00 00 02 C4 0B
RXD
01 03 04 00 00 00 00 FA 33
4x0003-4x0004
velocity
2
float
IEEE754
TXD
01 03 00 02 00 02 65 CB
RXD
01 03 04 00 00 00 00 FA 33
4x0005-4x0006
current
2
float
IEEE754
TXD
01 03 00 04 00 02 85 CA
RXD
01 03 04 00 00 00 00 FA 33
4x0007-4x0008
Cumulative decimal
2
Unsigned long
F4-F3-F2-F1
TXD
01 03 00 06 00 02 24 0A
RXD
01 03 04 00 00 00 00 FA 33
4x0009-4x0010
Cumulative decimal
2
float
IEEE754
TXD
01 03 00 08 00 02 45 C9
RXD
01 03 04 00 00 00 00 FA 33
4x0011-4x0012
Cumulative float
2
float
IEEE754
TXD
01 03 00 0A 00 02 E4 09
RXD
01 03 04 00 00 00 00 FA 33
4x0013-4x0014
Gas temperature
2
float
IEEE754
TXD
01 03 00 0C 00 02 04 08
RXD
01 03 04 BA 4A 41 F8 CF 2F
4x0015-4x0016
Current acquisition signal
value
2
float
IEEE754
TXD
01 03 00 0E 00 02 A5 C8
RXD
01 03 04 82 1F 40 36 52 5B
4x0017-4x0018
Lower Range
2
float
IEEE754
4x0019-4x0020
Upper Range
2
float
IEEE754
4x0021
Lower relay status
1
Unsigned int
0- open
1- close
4x0022
Upper relay status
1
Unsigned int
0- open
1- close
4x0051-4x0052
ID number
2
Unsigned long
F4-F3-F2-F1
4x0053
Device ID
1
Unsigned int
0-255
4x0054
BaudRate
1
Unsigned int
4x0055
Parity
1
Unsigned int
4x0056
StopBit
1
Unsigned int
Содержание TMS
Страница 1: ...Thermal Gas Mass Flowmeter Installation and Operation Guide...
Страница 11: ...11 4 3 Terminal connection Pulse output wiring Analog output wiring...
Страница 25: ...25 After entered the menu item press the ESC Key to return to the menu selection creen press the...
Страница 26: ...26 ENT key to enter the value set 7 2 4 Totalizer Settings Clear or set the cumulative flow decimal and integer...