TECHNICAL CHARACTERISTICS
070002_3_B
FGP 50/2 EVO-2
2
TECHNICAL CHARACTERISTICS
TECHNICAL
DATA
FGP 50/2 EVO-2
*
Reference
conditions:
Environment
temperature
20°C
-
Barometric
pressure
1013
mbars
-
Altitude
0
metre
(sea
level).
**
Measured
sonourous
pressure
in
the
combustion
lab,
with
funcional
burner
on
beta
boiler
in
a
distance
of
1
m
(UNI
EN
ISO
3746).
***
For
burner
FGP 50/2 EVO-2
with
long
head
add
1
kg
to
the
weight.
OPERATING
RANGE
DIAGRAM
FGP 50/2 EVO-2
The firing rates has been obtained based on test boilers in accordance with EN267 standards and are indicative of matching the burner to the boiler.
For the correct operation of the burner, combustion chamber dimensions must be in accordance with current regulation. In case of non-compliance,
contact the manufacturer.
MODEL
FGP 50/2 EVO-2
Flow min. 1°st. / min. 2°st. - max. 2°st. *
[kg/h]
9.9/20-53.1
Thermal power min. 1°st. / min. 2°st. - max. 2°st. *
[Mcal/h]
100.1/204-541.8
Thermal power min. 1°st. / min. 2°st. - max. 2°st. *
[kW]
117.4/237-630
Fuel: LIGHT-OIL 1.5°E at 20°C = 6.2 cSt = 35 sec Redwood N°1
Intermitted working operation (min. 1 stop every 24 hours) two stages
Environmental conditions operation / storage:
-15...+40°C / -20...+70°C, rel. humidity max. 80%
Max. temperature combustion air
[°C]
60
Nominal electric power
[kW]
1.1
Fan motor
[kW]
0.74
Nominal motor current absorption
[A]
1.8
Nominal auxiliary absorption
[A]
0.3
Power supply:
3~400V, 1N~230V - 50Hz
Electric protection degree:
IP 40
Noisiness ** min-max
[dBA]
71-73
Burner weight ***
[kg]
31
Fig. 1
X = Thermal power Y = Pression in the combustion chamber
0
2
4
6
8
10
12
0
200
400
500
600
700
[kW]
[mbar]
100
300