Maintenance and diagnostics
73
Fig. 34: LEDs on the supply side of the extended version
Tab. 87: LED overview
5.4
Troubleshooting
If unexpected malfunctions occur during operation according to the intended use, please
contact your support partner.
Designation
Interface
Function
State LED
all
Green (continuous light): Device active.
Green (flashing): Device active. However the state machine has not yet reached
the
Operation Enabled
state.
Red (continuously flashing): The drive has switched to a fault state. The output
stage will be switched off or has already been switched off.
Red (error code): Booting has failed. Please contact FAULHABER Support.
RUN LED
EtherCAT
Green (continuous light): Connection present. Device is ready for use.
Green (flashing): Device is in the
Pre-Operational.
state
Green (single flash): Device is in the
Safe-Operational.
state
Off: Device is in the
Initialisation
state.
ERR LED
EtherCAT
Red (flashing): Faulty configuration.
Red (single flash): Local error.
Red (double flash): Watchdog timeout.
Off: No connection error
LA LED
EtherCAT
Green (continuous light): No data transfer. Connection to another participant
established.
Green (flashing): Data transfer active.
Off: No data transfer. No connection to another participant.
Status LED
ERR LED RUN LED
LA LED
LA LED