-22-
6.2
Setting Current Output Range
Setting Current Output Range through SDO Communication
6.2.1
(Example) Setting Channel 2
①
Set LSET switch (SW3.1) of Output Range Setting Switch (SW3) to OFF before supplying power to the
module.
②
On the Output Connector (CN2), wire GND pin (G) and current output pin (I2) of Channel 2 to the
analogue device. Then, supply power to the module.
③
Enter the value of the Analogue Output Range Object (2301h) through the Master unit to set the
Current output range.
④
Supply power to the module again, and complete the setting.
Figure 6-3. Setting Current Output Range through SDO Communication
Setting Current Output Range with DIP Switches
6.2.2
(Example) Setting Channel 2
to 4~20[mA] Output Range
①
Set LSET switch (SW3.1) of Output Range Setting Switch (SW3) to ON before supplying power to the
module. Set the current output range of Channel 2 with SW3.5~SW3.6 switches (SW3.5=ON, SW3.6=ON).
②
On the Output Connector (CN2), wire GND pin (G) and current output pin (I2) of Channel 2 to the
analogue device. Then, supply power to the module.
Figure 6-4. Setting Current Output Range with DIP Switches
Содержание Ezi-IO EtherCAT DA
Страница 1: ...User Manual ...
Страница 9: ... 9 Configuration Chapter 2 2 1 Ezi IO EtherCAT DA Part Numbering 2 2 Ezi IO EtherCAT DA Part Number ...
Страница 10: ... 10 2 3 System Configuration ...
Страница 13: ... 13 3 3 Module Dimensions Unit mm Can be installed on 35mm DIN Rail Can be installed on 35mm DIN Rail ...
Страница 14: ... 14 Connection Panel View Chapter 4 4 1 Names and Functions Ezi IO EC DA04 T ...
Страница 20: ... 20 5 2 Internal Circuit Diagram Figure 5 4 Internal Circuit Diagram ...