-15-
EtherCAT ID
Setting Switches
(SW1, SW2)
4.1.1
Use two rotary switches to set EtherCAT ID (ECAT Device ID). Set ones digit (x1) of EtherCAT ID on the right
rotary switch (SW1), and set tens digit (x10) of EtherCAT ID on the left rotary switch (SW2).
Setting Range is 0 ~ 99.
* The Configured Alias ID set by the rotary switches is applied when the power is supplied to the I/O module.
Output Range Setting Switch (SW3)
4.1.2
Select the output range by SW3 referring to the chart.
① Selecting Output Setting Method
Select the output setting method with LSET switch (SW3.1).
* Set SW3.1 before supply power to the module.
* SW3.2 is not used.
② Selecting Output Range
When using the DIP Switch for the setting method (SW3.1=ON), select output range referring to the chart.
* 1~5 [V], 0~10 [V] voltage output range can be set by the SDO communication ONLY.
Switch
Setting Method
LSET
Description
SW3.1
DIP Switch
ON
Setting output range with DIP switches (SW3.3~SW3.10)
SDO Communication
OFF
Setting voltage/current output range through EtherCAT SDO communication
Switch
Output Range
CH1
CH2
CH3
CH4
SW3.3
SW3.4
SW3.5
SW3.6
SW3.7
SW3.8
SW3.9
SW3.10
0~5 [V]
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
-10~10 [V]
OFF
ON
OFF
ON
OFF
ON
OFF
ON
0~20 [mA]
ON
OFF
ON
OFF
ON
OFF
ON
OFF
4~20 [mA]
ON
ON
ON
ON
ON
ON
ON
ON
Содержание Ezi-IO EtherCAT DA
Страница 1: ...User Manual ...
Страница 9: ... 9 Configuration Chapter 2 2 1 Ezi IO EtherCAT DA Part Numbering 2 2 Ezi IO EtherCAT DA Part Number ...
Страница 10: ... 10 2 3 System Configuration ...
Страница 13: ... 13 3 3 Module Dimensions Unit mm Can be installed on 35mm DIN Rail Can be installed on 35mm DIN Rail ...
Страница 14: ... 14 Connection Panel View Chapter 4 4 1 Names and Functions Ezi IO EC DA04 T ...
Страница 20: ... 20 5 2 Internal Circuit Diagram Figure 5 4 Internal Circuit Diagram ...