4.7. Function 52. Circuit Breaker monitoring
This function allows the status of the circuit breaker to be monitored and preventive maintenance
to be performed, for which the following parameters need to be configured:
Group
Description
Minimum
Maximum
Step
Unit
Default
52
Circuit breaker monitoring
Maximum number of openings
1
10000
1
-
500
Maximum accumulated amperes
1
100000
1
M(A
2
)
1000
Opening time
0.02
30,0
0.01
s
0.10
Closing time
0.02
30,0
0.01
s
0.10
Maximum repeated openings
1
10000
1
-
3
Time of maximum repeated openings
1.00
300,0
0.01
min
9.00
NOTE:
The “Maximum accumulated amperes” adjustment units are M(A²) (square mega
amperes) whilst the “Accumulated amperes counter” units are K(A²) (square kilo amperes).
It is also necessary to assign the logical inputs 52a and/or 52b to a physical input.
This function provides information about the circuit breaker status and if any maintenance alarm
has been activated.
The following statuses are associated with this function:
Function
Status
Description
52
Start
Energized/Deenergized
These are the different statuses of the circuit breaker automatic control
Error
Open
Opening time
Opening error
Closed
Closing time
Closing error
No. of configured openings
exceeded
Activated if the counter that measures the number of openings exceeds the
"Maximum number of openings" setting
No. of configured
accumulated (l2t) amps
exceeded
Activated if the accumulated amps counter exceeds "Maximum accumulated
amps" setting
Repeated Trips
Activated the number of openings exceeds the setting in "Maximum
repeated openings" for the time set in "Time of maximum repeated
openings"
Содержание SIL-D00
Страница 8: ...www fanox com Rev 06 8 226 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view...
Страница 9: ...www fanox com Rev 06 9 226 2 2 Equipment dimensions...
Страница 10: ...www fanox com Rev 06 10 226 2 3 Cut out pattern...
Страница 12: ...www fanox com Rev 06 12 226 Digital connections Only as an example...
Страница 13: ...www fanox com Rev 06 13 226 2 5 Terminals...
Страница 49: ...www fanox com Rev 06 49 226...
Страница 50: ...www fanox com Rev 06 50 226...
Страница 51: ...www fanox com Rev 06 51 226...
Страница 52: ...www fanox com Rev 06 52 226...
Страница 111: ...www fanox com Rev 06 111 226 I C 3 7 0 00 A C I N 4 7 0 00 A C V R 5 7 0 00 V D Ang 6 7 0 00 deg C IMax 7 7 0 00 A...
Страница 200: ...www fanox com Rev 06 200 226...
Страница 224: ...www fanox com Rev 06 224 226 14 9 Comments Person in charge of commissioning Date Maintenance performed on the by...
Страница 225: ...www fanox com Rev 06 225 226 NOTES...
Страница 226: ...www fanox com Rev 06 226 226...