PROTECTION FUNCTIONS
4.1.
Functions 50_1 and 50_2. Instantaneous phase overcurrent
This protection function can be set by using three parameters:
Function
Description
Minimum
Maximum
Step
Unit
Default
50_1
50_2
Instantaneous phase overcurrent
Permission
-
-
Yes/No
-
No
Tap
0.10
30.00
0.01
Inominal
5.00
Operating time
0.02
300.00
0.01
s
0.02
The operating time is independent from the operating current flowing through the equipment, so if the
phase current exceeds its predetermined value for an equal or greater amount of time than this preset
value, the protection function activates (trips) and does not reset itself until the average value of the
phase drops below the point of current pick-up.
The function activates at 100% of the preset input, and deactivates at 95%. The reset is instantaneous.
The accuracy of the operating time is equal to the preset time plus a maximum of 30 ms.
4.2.
Function 67_1 & 67_2. Inverse-time phase directional overcurrent
Two phase directional units are available: 67_1 y 67_2.
This function uses the cross phase voltage as a polarization magnitude and the phase current as an
operating magnitude. The intervention sector is defined in the following way: the operating angle is
rotated anticlockwise from the polarization voltage, which gives us the maximum torque direction. A
cone is drawn, with the half-cone angle adjusted, over this maximum torque direction.
If the directionality option is not activated, the 67 function behaves like a 51P/50 function.
The actuation time starts when the following conditions are met simultaneously:
•
Polarization voltage higher than adjusted
•
Phase current higher than adjusted
•
The phase shift of phase current and polarization voltage is such that the phase current is
inside the intervention sector.
Содержание SIL B
Страница 1: ...EN_FANOXTD_MANU_SIL_Feeder_SILB_R023 Docx USER S MANUAL SIL B Feeder Relay...
Страница 8: ...www fanox com Rev 23 8 311 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view...
Страница 9: ...www fanox com Rev 23 9 311 2 2 Equipment dimensions...
Страница 10: ...www fanox com Rev 23 10 311...
Страница 11: ...www fanox com Rev 23 11 311 2 3 Cut out pattern CUT OUT PATTERN...
Страница 12: ...www fanox com Rev 23 12 311 2 4 Connection diagrams Analog connections...
Страница 13: ...www fanox com Rev 23 13 311...
Страница 14: ...www fanox com Rev 23 14 311 Digital connections Outputs and Trip circuit supervision...
Страница 15: ...www fanox com Rev 23 15 311 2 5 Terminals IEC 61850 or DNP3 0 protocols...
Страница 17: ...www fanox com Rev 23 17 311 IEC 60870 5 103 protocol...
Страница 25: ...www fanox com Rev 23 25 311 3 3 Functional diagram...
Страница 28: ...www fanox com Rev 23 28 311 3 5 1 SIL B 1 CHARGE CURVE 3 5 2 SIL B 5 CHARGE CURVE...
Страница 38: ...www fanox com Rev 23 38 311 4 6 4 Thermal protection curves This is the thermal curve for 3 minutes...
Страница 91: ...www fanox com Rev 23 91 311...
Страница 140: ...www fanox com Rev 23 140 311...
Страница 194: ...www fanox com Rev 23 194 311 Polarization V 35 0 V C Operating Angle 180 C Halfcone Angle 3 C...
Страница 307: ...www fanox com Rev 23 307 311 50BF init Fault init 79 Closure permission 52 closure permission...
Страница 308: ...www fanox com Rev 23 308 311 12 8 LED s configuration LEDs Blinking Latch Negate d LED On LED 1 LED 2 LED 3 LED 4 LED 5...
Страница 310: ...www fanox com Rev 23 310 311 NOTES...
Страница 311: ...www fanox com Rev 23 311 311...