www.fanox.com
Installation_Guide_SIAB000B0010AA_Rev. 03 6 / 32
1.4. Relay intallation
To fix the relay to the switchgear, use default holes in front of relay with appropriate fixing system. Do not
manipulate relay to fix it on the switchgear.
How to change the internal battery
1. Disconnect the relay. Switch the power supply off to avoid any dangerous situation.
2. Unscrew
the 4 screws on
the front of the relay to extract it from the RMU and access to the
rear side of the relay.
3. Unscrew
the 2 screws to remove the cover from the battery compartment.
4. Remove the battery and replace it respecting polarity (+ facing up):
Battery characteristics:
-
AA 3.6V lithium battery
-
Model LS14500 from SAFT
-
Do not use rechargeable batteries or other types of battery
5. Put on the battery cover and tighten the 2 screws.
6. Put the relay into the RMU again and tighten the 4 screws on the front to fix the relay.