www.fanox.com
Installation_Guide_SIAB000B0010AA_Rev. 03 10 / 32
4. TECHNICAL SPECIFICATIONS
Complete model
SIAB000B0010AA
0: Phase measurement
Defined by General Settings.
0: Neutral measurement
Internal measurement.
0: Net frequency
Defined by General settings.
B: Power supply
Self-p 230 Vac (Dual) + Commissonig battery
0: Additional functions
none.
0: Communications
USB (modubs RTU)
1: Inputs
–Outputs
Trip (for Striker) + External trip input (49T) + 1 magnetic indicator
0: Mechanics
Vertical. Assembly.
A: Languages
English, Spanish and German
A: Adaptation
-
Function
50
Permission: yes/no
Operating range: 0.20 to 20 x Is (step 0.01 x Is)
Operating time: 0.02 to 300 s (step 0.01 s)
Activation level 100%
Deactivation level 90%
Instantaneous deactivation
Timing accuracy: ± 40 ms or ± 0.5% (whichever is greater)
Function
50N
Permission: yes/no
Operating range: 0.20 to 20 x Is (step 0.01 x Is)
Operating time: 0.05 to 300 s (step 0.01 s)
Activation level 100%
Deactivation level 90%
Instantaneous deactivation
Timing accuracy: ± 40 ms or ± 0.5% (whichever is greater)
Function
50/51
Permission: yes/no
Operating range: 0.20 to 7 x Is (step 0.01 x Is)
Curves: IEC 60255-151 and IEEE
Operating time: IEC Inverse curve, IEC very inverse curve, IEC extremely inverse curve
IEC long time inverse, IEEE Inverse curve, IEEE very inverse curve, IEEE extremely
inverse curve.
Defined time: 0.02 to 300 s (step 0.01 s)
Dial: 0.05 to 1.25 (step 0.01)
Curve, activation level 110%
Curve, deactivation level 100%
Defined time, activation level 100%
Defined time, deactivation level 90%
Instantaneous deactivation