FANOX EMM-5 Скачать руководство пользователя страница 9

EMM-5 

instruction manual 

IM441-EU-F v0.4 

pag. 9  

ENTER IN THE SETUP
From the measures visualization, press at the same time the 

A

 and 

C

 keys, the message 

Set Up

 will appear on the 

F

displays.
CHOOSE THE DIGITAL OUTPUT TO PROGRAM
Press repeatedly the 

C

 key until the message 

SET  DO1

 (DO1 output) or 

SET  DO2

 (DO2 output) appears on the 

F

display. Press the 

A

 key to select this setting. 

SELECT THE MODALITY OF FUNCTIONING OF THE DIGITAL OUTPUT
To select the functioning mode, using the 

B

 and 

C

 keys, it’s possible to select: 

PULSE

 (pulse emission), 

ALR  SYS 

3PH

, (alarm on three phase value), 

ALR PH_ 123

 (alarm on minimum and maximum single phase value) and 

BY_

REMOTE

 (the digital output is managed using serial output). Press 

A

 key to confirm. 

CHOOSE THE PARAMETER TO LINK TO THE DIGITAL OUTPUT
With an alarm modality set, it’s necessary to select the parameters associated to the alarm output; by pressing the 

B

 and 

C

 keys until the parameter choice appears on the third part (L3) of 

F

 display and the glowing the corresponding led on the 

D

 bar. Press 

A

 key to confirm the set. 

SET THE HIGH AND THE LOW THRESHOLDS
On

F

 display will appear the message 

ALR Hi

 with the high threshold value; confirming with the 

A

 key on the same 

display will appear the message 

ALR LO

 with low threshold value. The 

B

 (to increase) and 

C

 (to decrease) keys are 

used to set the high and the low thresholds values. The range depends by the parameter and it is linked to the CT and VT 
ratios. Pressing 

A

 key to confirm. 

The threshold set is linked with CT and VT ratios, for this reason it’s necessary to make this operation after the 
programming of the CT and VT. The end scale value must be confirmed when CT and VT ratios are modified. 
The low threshold will be lower than high threshold. If the high threshold is set as OFF the low threshold will have the 
range of the high threshold. 
SET THE DELAY TO THE DIGITAL OUTPUT ACTIVATION
Now it’s possible to set the delay that will pass between the alarm condition set and the activation of digital output. On 

F

display will appear 

ALR DLY

 and the value expressed in seconds (range 1÷900). The modification of the value is done 

in the same way of the threshold set. With the confirmation (

A

 key) the set is complete. 

The programming will be referred to the digital output indicated on 

G

 display (

DO1

 o 

DO2

).

www.fanox.com

[email protected]

Tel: 0034 94 471 14 09

Fax: 0034 94 471 05 92

Pag 9

Содержание EMM-5

Страница 1: ...port serial port in alternative to the digital output power supply different from standard version current input 1A MEASURED PARAMETERS parameters unit of measurement initial identification phase and three phase voltages V kV V L1 N V L2 N V L3 N 6 V L N phase to phase and three phase system voltages V kV V L1 L2 V L2 L3 V L3 L1 6 V L L phase and three phase currents A kA A L1 A L2 A L3 6 A phase ...

Страница 2: ...le voltage 400V 300 500V phase to phase 175 290V phase neutral 230V 175 290V phase to phase 130 170V phase neutral L2 L3 phase to phase power supply 110V 85 145V phase to phase 50 85V phase neutral 230V 300 500V phase to phase 175 290V phase neutral L3 N phase neutral power supply 110V 175 290V phase to phase 100 170V phase neutral The standard version allows to apply the instrument at all the thr...

Страница 3: ... SINGLE PHASE LINE if the multimeters are used on single phase line the measure are referred at the L3 phase The others data displayed relatives at value of three phase system are not to consider I2 C I I1 I3 S1 S2 VL1 VL2 VL3 N EMM I2 C I I1 I3 S1 S2 VL1 VL2 VL3 N EMM I2 C I I1 I3 S1 S2 VL1 VL2 VL3 N EMM measure current inputs measure current inputs measure current inputs measure current inputs m...

Страница 4: ...t energy counters If it s selected with the A and B keys the display indicates the maximum and average values G display for the visualization of the electrical measure indicated in LED E energy counters excluded The voltage values are referred to the three phase system The k LED displays the reading in kilo x 1000 If it s selected with C key the display indicates the type of the energy displayed I...

Страница 5: ... 0 kW kVAr pulse 0 10 kW kVAr pulse 0 01 kW kVAr pulse seT TPL Increase from 100 to 500 mS in step by 100 mS Decrease version with digital output seT ID ADR Increase Set address of network from 001 to 127 Decrease version with serial output seT SER BDR Set baud rate 19200 baud 19 2 serial interface 9600 baud 9 60 version with serial output 4800 baud 4 80 2400 baud 2 40 seT PAR Set parameters of bi...

Страница 6: ...rease it press the C key To confirm it press the A key The average time is the time used to calculate the average parameters avg and the maximum demand maxD Programming of the energy visualization type seT EN This setting allows to define the energy visualization type after the visualization of the temperature With TOT PAR will have the visualization of the partial and total energy counters With N...

Страница 7: ...he enter of the setup use the A B and C keys as the same way done previously The menu is cyclic After the last setting the instrument go back to the first page of Setup SETUP It s always possible to come back to measures visualization mode pressing at the same time the A and C keys PEAK VALUES AND ENERGY COUNTERS RESET RESET From the measures visualization mode pressing the A and C keys simultaneo...

Страница 8: ... HI and ALR LO With ALR SYS 123 the digital output will function as alarm verifying that the maximum value of the single phases doesn t exceed the maximum threshold set ALR HI and that the minimum value of the single phases doesn t come down the minimum threshold set ALR LO The activation of the alarm output will come after some seconds of delay set ALR DL In the REMOTE mode the output status will...

Страница 9: ...OLDS On F display will appear the message ALR Hi with the high threshold value confirming with the A key on the same display will appear the message ALR LO with low threshold value The B to increase and C to decrease keys are used to set the high and the low thresholds values The range depends by the parameter and it is linked to the CT and VT ratios Pressing A key to confirm The threshold set is ...

Страница 10: ...and the A key to confirm it SET THE THRESHOLD Subsequently it s necessary to set the threshold using the B to increase and C to decrease keys Confirm with A key I O INFO PAGE After the hour counter set the I O info page appears in F displays on the second part L2 the status of the first digital output DO1 on the third part L3 the status of the second digital output DO2 The visualization of the sta...

Страница 11: ...ton to select the parameter that can be displayed and indicated from E LED The voltage values are of the three phase system the frequency is of the L1 channel Visualization energy and hours counters With the C key it s possible to visualize on F display the active reactive and apparent energy counters One segment of the right digit of the G display in correspondence of the kWh and KVArh on the fro...

Страница 12: ...xD avg I L1 max avg I L2 max avg I L3 max avg phase currents maximum of average phase currents max demand max maxD avg 6 W max avg 6 VAr max avg 6 VA max avg three phase power maximum of average three phase powers maximum demand max maxD avg I L1 avg I L2 avg I L3 avg phase currents average phase currents max maxD avg 6 W avg 6 Var avg 6 VA avg three phase power average three phase powers max maxD...

Страница 13: ...32 485 converter between the RS232 PC s outlet and the instrument s it s necessary to insert a line termination resistance Rt 100 120 ohm between the twisted pair of cables placing it between the converter and the end of the network last instrument connected Use always twisted cables with minimum section of 0 36mm2 22AWG and lower capacity of 60 pF m i e BELDEN cable type EIA RS485 Ref 3105A Shiel...

Страница 14: ...EMM 5 instruction manual IM441 EU F v0 4 pag 14 DIMENSIONS 92 92 R3 96 96 90 96 56 9 20 cut panel www fanox com fanox fanox com Tel 0034 94 471 14 09 Fax 0034 94 471 05 92 Pag 14 ...

Страница 15: ...single phase insertion in MT with external TV and transforming rate programmable from 0 1 to 400 0 current inputs from 0 02 to 5A permanent overload 30 from external TA with secondary 5A primary programmable from 5 to 10000A auto consumption 0 5VA INPUTS OUTPUTS digital outputs Two outputs with common optomos 12 230Vac dc max 150mA Insulation 3kV for 60 second Pulse Function Weight programmable 0 ...

Страница 16: ...M425 UE F v2 2 pag 16 Parque Tecnológico de Bizkaia Edif 604 48160 DERIO BIZKAIA ESPAÑA Tel 0034 94 471 14 09 Fax 0034 94 471 05 92 E mail fanox fanox com Web www fanox com www fanox com fanox fanox com Tel 0034 94 471 14 09 Fax 0034 94 471 05 92 Pag 16 ...

Отзывы: