FANOX EMM-5 Скачать руководство пользователя страница 6

EMM-5 

instruction manual 

IM441-EU-F v0.4 

pag. 6  

Programming of the transformation ratio of the external current transformers (

SET CT

)

The programming of the CT ratio, intended as the ratio between the primary and the secondary circuit (example: with CT 
1000/5 it must be set 200), has to be performed by using the front keys. 
After the enter in the setup (message 

SETUP

 on 

F

 display) pressing the 

C

 key, the message 

seT

 will appear on the 

G

display and the message 

CT

(Current transformer ratio) on the first 

F

 display; the transformation ratio value (set to 1 by 

the manufacturer) on the second and the third 

F

 display. Press 

B

 or 

C

 keys to increase or decrease the value 

respectively (the variation is performed unit by unit). In order to speed up the operation, keep the 

B

 or 

C

 key pressed, the 

variation will be performed by tens and hundreds. To increase or decrease the value by unit, it is necessary to release 
and to press the button again. To confirm the set value, press the 

A

 button; in this way it is possible to enter the next 

programming. If none key is pressed for 10 seconds, the instrument will automatically leave the programming menu and 
the eventual setting SHALL NOT be stored. 

-  Programming of the transformation ratio of the external voltage transformers (

SET VT

)

After the precedent programming phase, on 

F

 display will appear the inscription 

Vt

 (voltage transformer) and the value 

of the transformation rate of the external TV (set to 1 from the constructor), considered as the rate between primary and 
secondary (example with TV 15/0.1 kV the value will be 150). In the same way at the programming of the CT rate will be 
possible to set this value. If the external TV are not used the value to set will be 1. To confirm the value press the 

A

button.

If the instrument has not options the programming continues with the set of average time 

AVG  T’

 and after with the 

password

PASS

, then it come back at the first page 

SETUP

. The presence or the absence of the options, neutral 

current, digital output and serial output, will allow the visualization or not of the other settings. 

Programming of the average time (

seT AVG T’

)

After the programming phase previously described, pressing another time the 

A

 key, on the 

F

 display will appear the 

message

AVG T’

 and the average time settable from 1 to 30 minutes. 

To increase the value press the 

B

 key. To decrease it, press the 

C

 key. To confirm it press the 

A

 key. 

The average time is the time used to calculate the average parameters (

avg

) and the maximum demand (

maxD

).

Programming of the energy visualization type (

seT EN

)

This setting allows to define the energy visualization type after the visualization of the temperature. 
With

TOT PAR

 will have the visualization of the partial and total energy counters. With 

NORMAL

 there will be only the 

visualization of total counters (that it’s possible to reset from 

RESET

 menu). 

Programming insertion mode (

3PH

)

In a unbalance three phase system it’s necessary to set 

UN_BAL

 (unbalance) while in a balance system (only one CT 

and only one VT) the correct set is 

BALANC

 (balance). 

Programming wiring connection mode (

MDE

)

This setting allows to definite the wiring type connection. It’s possible to chose 3 wires or 4 wires. With the 4 wires 
connection the neutral parameter are displayed and enabled to use for the digital and analog outputs settings. 

Programming of the synchronism type (

SYN MDE

)

In this setting for the synchronization type, it’s possible to choose 

L3

 to use the external frequency (on L3 phase) or 

50

,

60

 Hz to use the internal clock. 

Programming of the weight of the active and reactive energy pulse (

seT PULSE

) (only for vers. with digital output)

After the above mentioned programming, by pressing the 

A

 key again, the message 

Pulse

 will appear on the 

F

 display 

and the value of the weight of one pulse settable on three phase values: 

0,01

 - 

0,1

-

1

-

10

 kWh or kVArh (for each 

emitted pulse the instrument will have counted 0,01 - 0,1 - 1 - 10 kWh o kVArh). 
Press the 

B

 key to increase the value or 

C

 key to decrease the value and 

A

 to confirm. 

Programming of the duration pulse (

SET TPL

) (only for vers. with digital output)

The message 

TP

L

 will appear together the value of the duration pulse expressed in mS. It’s possible to select the value 

from 100 mS to 500 mS, with 100 ms steps by using 

B

 key (to increase the value) and 

C

 (to decrease the value). Confirm 

the value pressing the 

A

 key. 

This setting is used by all digital outputs. 

Programming of the address for the communication network (

SET ID ADR

) (only for vers. with serial output)

After the confirm with the 

A

 key of the previous value, the message 

ID aDR

 will appear on

F

 display; to set the value 

that will identify the instrument when it will be connected in a EIA485 communication network, proceed with the modality, 
already described. The settable values are from 1 to 247. To confirm, press the 

A

 key. 

www.fanox.com

[email protected]

Tel: 0034 94 471 14 09

Fax: 0034 94 471 05 92

Pag 6

Содержание EMM-5

Страница 1: ...port serial port in alternative to the digital output power supply different from standard version current input 1A MEASURED PARAMETERS parameters unit of measurement initial identification phase and three phase voltages V kV V L1 N V L2 N V L3 N 6 V L N phase to phase and three phase system voltages V kV V L1 L2 V L2 L3 V L3 L1 6 V L L phase and three phase currents A kA A L1 A L2 A L3 6 A phase ...

Страница 2: ...le voltage 400V 300 500V phase to phase 175 290V phase neutral 230V 175 290V phase to phase 130 170V phase neutral L2 L3 phase to phase power supply 110V 85 145V phase to phase 50 85V phase neutral 230V 300 500V phase to phase 175 290V phase neutral L3 N phase neutral power supply 110V 175 290V phase to phase 100 170V phase neutral The standard version allows to apply the instrument at all the thr...

Страница 3: ... SINGLE PHASE LINE if the multimeters are used on single phase line the measure are referred at the L3 phase The others data displayed relatives at value of three phase system are not to consider I2 C I I1 I3 S1 S2 VL1 VL2 VL3 N EMM I2 C I I1 I3 S1 S2 VL1 VL2 VL3 N EMM I2 C I I1 I3 S1 S2 VL1 VL2 VL3 N EMM measure current inputs measure current inputs measure current inputs measure current inputs m...

Страница 4: ...t energy counters If it s selected with the A and B keys the display indicates the maximum and average values G display for the visualization of the electrical measure indicated in LED E energy counters excluded The voltage values are referred to the three phase system The k LED displays the reading in kilo x 1000 If it s selected with C key the display indicates the type of the energy displayed I...

Страница 5: ... 0 kW kVAr pulse 0 10 kW kVAr pulse 0 01 kW kVAr pulse seT TPL Increase from 100 to 500 mS in step by 100 mS Decrease version with digital output seT ID ADR Increase Set address of network from 001 to 127 Decrease version with serial output seT SER BDR Set baud rate 19200 baud 19 2 serial interface 9600 baud 9 60 version with serial output 4800 baud 4 80 2400 baud 2 40 seT PAR Set parameters of bi...

Страница 6: ...rease it press the C key To confirm it press the A key The average time is the time used to calculate the average parameters avg and the maximum demand maxD Programming of the energy visualization type seT EN This setting allows to define the energy visualization type after the visualization of the temperature With TOT PAR will have the visualization of the partial and total energy counters With N...

Страница 7: ...he enter of the setup use the A B and C keys as the same way done previously The menu is cyclic After the last setting the instrument go back to the first page of Setup SETUP It s always possible to come back to measures visualization mode pressing at the same time the A and C keys PEAK VALUES AND ENERGY COUNTERS RESET RESET From the measures visualization mode pressing the A and C keys simultaneo...

Страница 8: ... HI and ALR LO With ALR SYS 123 the digital output will function as alarm verifying that the maximum value of the single phases doesn t exceed the maximum threshold set ALR HI and that the minimum value of the single phases doesn t come down the minimum threshold set ALR LO The activation of the alarm output will come after some seconds of delay set ALR DL In the REMOTE mode the output status will...

Страница 9: ...OLDS On F display will appear the message ALR Hi with the high threshold value confirming with the A key on the same display will appear the message ALR LO with low threshold value The B to increase and C to decrease keys are used to set the high and the low thresholds values The range depends by the parameter and it is linked to the CT and VT ratios Pressing A key to confirm The threshold set is ...

Страница 10: ...and the A key to confirm it SET THE THRESHOLD Subsequently it s necessary to set the threshold using the B to increase and C to decrease keys Confirm with A key I O INFO PAGE After the hour counter set the I O info page appears in F displays on the second part L2 the status of the first digital output DO1 on the third part L3 the status of the second digital output DO2 The visualization of the sta...

Страница 11: ...ton to select the parameter that can be displayed and indicated from E LED The voltage values are of the three phase system the frequency is of the L1 channel Visualization energy and hours counters With the C key it s possible to visualize on F display the active reactive and apparent energy counters One segment of the right digit of the G display in correspondence of the kWh and KVArh on the fro...

Страница 12: ...xD avg I L1 max avg I L2 max avg I L3 max avg phase currents maximum of average phase currents max demand max maxD avg 6 W max avg 6 VAr max avg 6 VA max avg three phase power maximum of average three phase powers maximum demand max maxD avg I L1 avg I L2 avg I L3 avg phase currents average phase currents max maxD avg 6 W avg 6 Var avg 6 VA avg three phase power average three phase powers max maxD...

Страница 13: ...32 485 converter between the RS232 PC s outlet and the instrument s it s necessary to insert a line termination resistance Rt 100 120 ohm between the twisted pair of cables placing it between the converter and the end of the network last instrument connected Use always twisted cables with minimum section of 0 36mm2 22AWG and lower capacity of 60 pF m i e BELDEN cable type EIA RS485 Ref 3105A Shiel...

Страница 14: ...EMM 5 instruction manual IM441 EU F v0 4 pag 14 DIMENSIONS 92 92 R3 96 96 90 96 56 9 20 cut panel www fanox com fanox fanox com Tel 0034 94 471 14 09 Fax 0034 94 471 05 92 Pag 14 ...

Страница 15: ...single phase insertion in MT with external TV and transforming rate programmable from 0 1 to 400 0 current inputs from 0 02 to 5A permanent overload 30 from external TA with secondary 5A primary programmable from 5 to 10000A auto consumption 0 5VA INPUTS OUTPUTS digital outputs Two outputs with common optomos 12 230Vac dc max 150mA Insulation 3kV for 60 second Pulse Function Weight programmable 0 ...

Страница 16: ...M425 UE F v2 2 pag 16 Parque Tecnológico de Bizkaia Edif 604 48160 DERIO BIZKAIA ESPAÑA Tel 0034 94 471 14 09 Fax 0034 94 471 05 92 E mail fanox fanox com Web www fanox com www fanox com fanox fanox com Tel 0034 94 471 14 09 Fax 0034 94 471 05 92 Pag 16 ...

Отзывы: