Chapter 6 Function Introduction
Shenzhen Hpmont Technology Co., Ltd.
- 52 -
MONT72 Series User Manual V1.0
6.2.4
F03: Acc. / Dec. Parameters
Ref. Code
Function Description
Setting Range [Default]
F03.00
Acc. speed
0.020 - 9.999 [0.700m/s
2
]
F03.01
Start Acc. jerk
0.020 - 9.999 [0.350m/s
3
]
F03.02
End Acc. jerk
0.020 - 9.999 [0.600m/s
3
]
F03.03
Dec. speed
0.020 - 9.999 [0.700m/s
2
]
F03.04
Start Dec. jerk
0.020 - 9.999 [0.600m/s
3
]
F03.05
End Dec. jerk
0.020 - 9.999 [0.350m/s
3
]
F03.00 - F03.05 adjust the elevator speed via S-curve
which can cushion the shock at elevator start / stop
and improve riding comfort.
•
Acc. jerk: The change ratio of Acc.
•
See the right figure for the adjustment of S-curve.
•
The S-curve becomes steeper when parameter
values are raised;
•
The S-curve becomes slower when parameter
values are decreased.
F03.06
Inspection Acc. speed
0.020 - 9.999 [0.200m/s
2
]
F03.07
Inspection Dec. speed
0.020 - 9.999 [1.000m/s
2
]
Defines the Acc. / Dec. speed of elevator at inspection run mode.
F03.08
Battery driven Acc. speed
0.020 - 9.999 [1.000m/s
2
]
F03.09
Battery driven Dec. speed
0.020 - 9.999 [1.000m/s
2
]
Defines the Acc. / Dec. speed of elevator at battery driven mode.
F03.10
Auto-tuning Acc. speed
0.020 - 9.999 [0.100m/s
2
]
F03.11
Auto-tuning Dec. speed
0.020 - 9.999 [0.100m/s
2
]
Defines the Acc. / Dec. speed at auto-tuning of motor.
F03.12
Abnormal Dec. speed
0.020 - 9.999 [1.000m/s
2
]
Defines the Dec. speed at valid forced or wrong run mode.
F03.13
Stop Dec. jerk
0.020 - 9.999 [0.350m/s
2
]
Defines Dec. change rate from non-zero speed to zero speed.
•
It can adjust the smooth stop of the elevator and ass riding comfort.
F03.14
Asyn. motor field-weakening optimization
0 - 2 [0]
0: No field-weakening optimization.
1: Optimize according to voltage.
2: Optimize according to current.
F03.14 = 1 or 2, it can reduce the current noise and improve the dynamic performance of asyn. motor.
F03.15
Field-weakening Kp
0 - 5000 [4000]
F03.16
Field-weakening Ki
0 - 5000 [1000]
F03.17
Field-weakening voltage limit
4000 - 5000 [4126]
F03.15 - F03.17 is used to adjust the effect of asyn. motor field-weakening so that user need not regulate
them usually.
F03.19
Sincos encoder CD phase learning
0,1 [0]
0: Learning.
1: Not learning.
0
Speed
Target
speed
Time
F03.02
F03.04
F03.01
F03.05
F03.00
F03.03
F03.13
Содержание MONT72 Series
Страница 1: ...V1 0 2018 09 MONT72 Series Elevator Controller User Manual MONT72 Series Elevator Controller ...
Страница 3: ...Version and Revision Records Version time 2018 9 Version V1 0 Chapter Content V1 0 issue ...
Страница 7: ......
Страница 9: ......
Страница 15: ......
Страница 43: ......
Страница 81: ......
Страница 99: ......