Chapter 6 Function Introduction
MONT72 Series User Manual V1.0
- 49 -
6.2
Group F: General Function Parameters
6.2.1
F00: Basic Parameters
Ref. Code
Function Description
Setting Range [Default]
F00.00
Motor type
0,1 [0]
0: Asyn. motor.
1: Syn. motor.
F00.01
Control mode
0 - 2 [2]
0: V/f control. Constant voltage / frequency ratio control.
•
It is applicable for special elevator occasion. This mode does not need the encoder and the control
effect is not so good as the vector control.
•
When select V/f control, properly set the V/f control parameter of Group F07 to achieve proper
efficiency.
1: SVC control. Sensorless vector control. It is only applicable for asyn. motor.
2: Closed-loop vector control. Sensor vector control.
•
Closed-loop vector and applicable for high accuracy speed control occasion. Generally the elevator will
take this mode.
Note:
1. V/f and SVC control are temporary running modes applicable when the motor does not install encoder and the
elevator is in inspection running.
2. Set motor parameter auto-tuning when select SVC or closed-loop vector control mode.
Auto-tuning steps: Correctly set the motor nameplate parameters (F07.00 - F07.04 / F10.00 - F10.05), then start
the motor parameter auto-tuning to obtain the right parameters. Meanwhile set vector control parameters of
Group F08 to achieve excellent vector control efficiency.
F00.02
Rated speed of elevator
0.100 - 4.000 [1.500m/s]
Refers to nominal rated speed of elevator. All speed setting value in the parameters must < F00.02.
F00.03
Max. output frequency
5.00 - 100.00 [50.00Hz]
Defines the max. frequency that MONT72 is allowed to output.
Be careful to set reasonable parameters according to the nameplate of the motor and the actual operating
conditions.
F00.04
Mechanical parameters of motor
10.0 - 6000.0 [60.0]
Defines the relationship between the elevator speed and the motor rotary speed.
•
The mechanical parameters are calculated based on the motor parameters. They determine the control
precision and must be correctly set.
The relationship of elevator speed and rotary speed of motor is:
Elevator speed (m s
⁄
) =
Rotary speed of motor (rpm)
60
×
F00.04
1000
The formula for calculating F00.04 is:
F00.04 =
π
× D
i × Winding mode
D: Diameter of motor (mm); i: Dec. rate;
Winding mode: The way that the hoist cable is wound, set according to the actual elevator setting.
F00.05
Operating mode
0 - 2 [0]
0: Keypad control.
•
Controlled by pressing the
or
key of the keypad. Set the run speed in F00.07.
1: Terminal analogue control.
•
The run command is controlled by UP and DN of the terminal; And the run speed is set by analogue
input terminals.
6
Содержание MONT72 Series
Страница 1: ...V1 0 2018 09 MONT72 Series Elevator Controller User Manual MONT72 Series Elevator Controller ...
Страница 3: ...Version and Revision Records Version time 2018 9 Version V1 0 Chapter Content V1 0 issue ...
Страница 7: ......
Страница 9: ......
Страница 15: ......
Страница 43: ......
Страница 81: ......
Страница 99: ......