40
threshold is disabled and the alarm will not be triggered. The valid range for the Temperature
threshold setting is 5 to 65, and 5 to 95 for Humidity.
Calibration Offset
If the measurement value of a sensor doesn't, for whatever reason, comply with the actual
environment, the 'Calibration Offset' setting can be configured to adjust the final value of the
sensor. For example, if a sensor reports 43% humidity for a 45% humidity environment, the user
can configure the humidity offset as 2% so the sensor can then adjust its final value to 45%.
Alarm Type
If an alarm sensor (water leak, security, etc) is connected to the USHA, the user can configure the
alarm as 'Disabled', 'Normal Open', or 'Normal Close'. A 'Disabled' setting will mean the alarm is
inactive.
'Normal Open' and 'Normal Close' are used for a two-wire detector that will emulate an
open/close state. When the wires are closed to 'loopback' (the signal for the sensor), the sensor
will detect the state as closed. The sensor will NOT activate the alarm for 'Normal Close' in this
case, although the alarm will be activated if configured as 'Normal Open'.
EMD Status
The EMD can be configured as 'Disabled' or 'Auto'. The setup should be configured as 'Disabled' if
an EMD is not attached to the port. The EMD type will be auto detected by the USHA if configured
as 'Auto' and if the EMD is plugged into the port.
Wireless Configuration
Wireless Configuration display the wireless status and allow administrator to configure the basic
settings for your wireless network.
Wireless Status
Wireless Control
This field display the wireless function was enabled or disabled.
Connection Status
This field display the wireless connection status.
BSSID
The MAC address of wireless device.
IP Address
The IP address which assigned by wireless device.