Falcon SG2K-1T-HW Скачать руководство пользователя страница 1

OWNER'S

OPERATING

MANUAL

Hardwire Uninterruptible Power Supply Models:

SG2K-1T-HW
SG2K-2T-HW
SG3K-1T-HW
SG3K-2T-HW

Detailed SG Series product specifications are available in PDF format at 

www.falconups.com

®

2006 Falcon

®

Electric Inc. All rights reserved.

All other brand names and trademarks are the property of their respective owners.
The information stated in this document is subject to change without notice.  2006-04-05
Falcon

®

, Falcon® Electric and UPS Plus logos are registered trademarks of Falcon Electric Inc

Rev. NR

FALCONElectric Inc., 5116 Azusa Canyon Rd., Irwindale, California  91706, (626) 962-7770, Fax 626-962-7720, Email: [email protected]

Содержание SG2K-1T-HW

Страница 1: ...ectric Inc All rights reserved All other brand names and trademarks are the property of their respective owners The information stated in this document is subject to change without notice 2006 04 05 F...

Страница 2: ...apter 3 Operation 12 Front Panel Indicators Function Key Diagram 12 Front Panel Function Description 12 Audible Alarms 14 Category One Alarms 14 Category Two Alarms 14 Chapter 4 Rear Panel Details 15...

Страница 3: ...ut Precision Output Voltage Regulation Superior Brownout Surge and Transient Protection Internal System Bypass Eliminates Generator Frequency Voltage Drift Microprocessor Control RS 232 Communications...

Страница 4: ...r supervised by personnel knowledgeable of batteries and the required precautions Keep unauthorized personnel away from batteries When replacing the UPS batteries use the same number and type of batte...

Страница 5: ...sition the Green Mode function is activated When the load connected to the output of the UPS drops to under 10 of the full rated UPS output for 30 seconds the UPS is automatically placed into bypass a...

Страница 6: ...wn and monitoring are desired connect the green UPS Computer cable to the DB 9 connector located on the UPS rear panel Then install the shutdown and monitoring software provided with the UPS For your...

Страница 7: ...y Down Down 208 Vac 115 Vac Down Up 220 Vac default 120 Vac Up Down 230 Vac 125 Vac Up Up 240 Vac 130 Vac SW3 FUNCTION Down GREEN MODE ON Up GREEN MODE OFF SWITCH SETTINGS FOR ALL MODELS GREEN MODE SW...

Страница 8: ...c 50 60Hz 11 2A 1 phase 2 wire plus ground 20A WIRE GAUGE CHART MODEL AC INPUT 1 120 Vac 2 208 240 Vac AC OUTPUT S 120 Vac 208 240 Vac SG2K 1T HW 10 Awg 600V 75 C CU 10 Awg 600V 75 C CU N A SG2K 2T HW...

Страница 9: ...W Output 1 200 220 230 or 240Vac selectable 1 phase 2 wire plus ground 20A 1 2 3 4 5 View of the Input Output Hardwire Terminal Block This terminal block is located on the UPS rear panel and shown wit...

Страница 10: ...nabled position the Green Mode function is activated When the load connected to the output of the UPS drops to under 10 of the full rated UPS output for 30 seconds the UPS is automatically placed into...

Страница 11: ...BE INSTALLED IN AN ENCLOSED AREA 9 Turn the input circuit breaker located on the UPS rear panel to the on position The internal UPS fan and front panel line indicator should turn on followed by the by...

Страница 12: ...the following a Verify the battery charger circuit breaker is in the off down position b On the battery bank nameplate label located on the rear panel verify the battery charger input voltage matches...

Страница 13: ...4A 82 5Vdc 4A 82 5Vdc 4A 82 5Vdc 4A OF CHARGERS 1 1 1 1 2 3 FOR 2KVA HW MODELS BATTERY OPTION MODELS W O Charger SGB2S7 3K3 SGB2S7 3K3 SGB5S7 3K6 SGB2S7 3K3 SGB5S7 3K6 SGB5S7 3K6 BATTERIES 16 Pieces...

Страница 14: ...Second LED is let when the battery level is above the low battery warning Level The first LED is lit when the battery level is above the battery cutoff voltage 3 LINE SITE WIRING FAULT INDICATOR LED F...

Страница 15: ...he following describes the different modes of operation for this button a Depressing this button when the UPS is off and the utility voltage is not present or with the UPS input circuit breaker in the...

Страница 16: ...TEST BUTTON DEPRESSED 2 Category two alarms a Three short beeps indicate the SG UPS output voltage is out of proper operating range SG UPS OUTPUT VOLTAGE IS OUT OF PROPER RANGE b Four short beeps indi...

Страница 17: ...FLOW RS 232 Port Secondary Input Circuit Breaker Dip Switches Battery fuse as received in bag At the time of initial installation remove the bag from the unit and install the battery fuse Battery Fuse...

Страница 18: ...the green cable supplied with the UPS There are communications options that WILL DISABLE the RS 232 port and render it inoperable The options are as follows a Internal SNMP HTTP agent option installe...

Страница 19: ...ommons JP3 open Alarm common only PIN JUMPER ASSIGNMENT FOR THE FALCON UA88374 RELAY OPTION BOARD no on bypass signal PIN JUMPER ASSIGNMENT FOR THE FALCON UA88376 RELAY OPTION BOARD with on bypass sig...

Страница 20: ...upon utility loss 4 Common for pins 2 3 5 5 Low Battery N O Closes at low battery 6 Remote Shutdown Applying a 5 12Vdc voltage level for 500ms while the UPS is on battery will shutdown the UPS 7 Not U...

Страница 21: ...Shutdown on battery operation only 2 Remote Shutdown Common 3 Not Used 4 Low Battery Common 5 Low Battery N O 6 Not Used 7 Not Used 8 Utility Fail 10Vdc 9 Utility Fail 10Vdc PIN JUMPER ASSIGNMENT FOR...

Страница 22: ...Falcon Service Department see page 20 for contact information Never attempt to service batteries High voltage exists within the unit which could cause electrical shock Servicing of batteries should b...

Страница 23: ...l interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the inst...

Страница 24: ...eturning any SG Series product Falcon Electric will not assume any responsibility for shipping damage In the event of shipping damage you will be notified of the damage and be instructed to file a cla...

Страница 25: ...NY IMPLIED WARRANTY OF MERCHANTABILITY IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE AND EXPRESS WARRANTIES THAT THIS PRODUCT WILL CONFORM TO ANY AFFIRMATION OR PROMISE FOR THIS PRODUCT AND THE...

Страница 26: ...15R or 3 5 15R 2 5 20R 6 IEC 320 or 1 L6 20R 6 5 15R or 3 5 15R 2 5 20R 6 IEC 320 or 1 L6 20R 2 5 20R 1 L6 20R HW Models Hardwire Hardwire Not Available Contact the factory for other input output opt...