Installation & User Manual Falcon Electric, Inc.
FN2 Series OM480051 Rev.: E
40
Options
Communication
Software:
UPSilon Monitoring (Reference UPSilon manual for installation instructions.)
1. Connect supplied USB cable between UPS and PC workstation.
Dry Contact Relay Card (Falcon Item #: UA88383)
Pin 1: UPS on Bypass mode
Pin 2: Utility Abnormal
Pin 3: Utility Normal
Pin 4: Inverter On
Pin 5: Battery Low
Pin 6: Battery Abnormal
Pin 7: UPS Alarm
Pin 8: Common
Pin 9: Shutdown UPS positive (+) signal
Pin 10: Shutdown UPS negative (-) signal
Notes:
•
The shutdown function will be activated after +6 to +25 VDC is applied between pin 9
and pin 10 for 5 seconds.
•
The capacity of each relay contact is 40 VDC/25mA.
•
Installation Position: Slot 1 (CHA-CN7) or Slot 2 (CHB-CN8).
•
Flexible signal output for N.C. (Normal close) or N.O. (Normal open) contact by shorting
pins 1-2 or pins 2-3 from JP1-5.
•
The shutdown function will be enabled 1 minute after blackout occurs if pins 1-2 of both
CN1 and CN6 are shorted. Otherwise the shutdown function can be enabled only by
pins 9-10 of CN3 if pins 2-3 of both CN1 and CN6 are shorted.
Содержание FN2-4.5K-2TXI
Страница 2: ......
Страница 12: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev E 12 Accessories Kit...
Страница 26: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev E 26 I1 J K L M N...
Страница 27: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev E 27 O O1 P O2...
Страница 29: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev E 29 S2 T U V1 V2 V3...
Страница 39: ...Installation User Manual Falcon Electric Inc FN2 Series OM480051 Rev E 39...