This chapter describes solely the cables to be used in the installation of
the QC-PDS system and the characteristics of the connectors of those
cables. Its mechanical characteristics are also detailed.
The Installation chapter in this manual describes the cabling of the QC-
PDS system for the power lines, feedback, optic fiber of the SERCOS-II
ring o SERCOS-III Ethernet line topology cable, communications and
others are described in the following chapter on installation manual.
The attached
table determines the minimum cable section required
for the maximum allowable current in a continuous duty circulating
through copper conductors that are installed inside PVC conduits or
channels
·
least favorable installation method
·
.
MANDATORY.
The length of any cable used in the installation of the QC-
PDS system must be shorter than 30 m, except for the power (motor),
feedback (encoder) and fiber optic (SERCOS-II interface) cables or the
Ethernet (SERCOS-III interface) cables, which may exceed this length.
MANDATORY.
The dielectric insulation of the cable must be enough to
withstand the test voltage at a minimum of 2 000 V AC for 5 minutes for
cables supporting voltages over 50 V AC (alternating current) or 120 V
DC (direct current). Refer to the recommendations of the cable
manufacturer before doing the installation.
T. H7/1
Admissible section/Inmax.
Section Inmax.
Section Inmax.
Section Inmax.
Section Inmax.
mm²
A
mm²
A
mm²
A
mm²
A
1.5
13.1
6
30
25
70
70
130
2.5
17.4
10
40
35
86
95
156
4
23
16
54
50
103
120
179
Cable section with PVC insulation and copper conductor for maximum permissible
rated current, based on UNE-EN 60204-1,
table 6, installation method B2
, for
ambient air temperature at
40 °C
.
Section Inmax.
Section Inmax.
Section Inmax.
Section Inmax.
mm²
A
mm²
A
mm²
A
mm²
A
150
262
Cable section with PVC insulation and copper conductor for maximum permissible
rated current, based on IEC 60364-5-52,
table B-52-4, installation method B1
,
for ambient air temperature at
30 °C
.
NOTE.
For other installation methods, consult the values provided for in
UNE-EN 60204-1 and IEC 60364-5-52.
Содержание QC-PDS
Страница 1: ...DRIVE QC PDS Hardware manual Ref 2003...
Страница 6: ...6 I 6 Ref 2003 6 QC PDS HARDWARE This page intentionally left blank...
Страница 16: ...16 Ref 2003 16 Previous I QC PDS HARDWARE This page intentionally left blank...
Страница 18: ...18 Ref 2003 18 Previous II QC PDS HARDWARE This page intentionally left blank...
Страница 80: ...2 POWER SUPPLIES Power supplies 80 Ref 2003 QC PDS HARDWARE...
Страница 138: ...3 DRIVES Drives 138 Ref 2003 QC PDS HARDWARE...
Страница 174: ...4 AUXILIARY MODULES Auxiliary modules Ref 2003 174 QC PDS HARDWARE...
Страница 302: ...8 INSTALLATION Installation Ref 2003 302 QC PDS HARDWARE...
Страница 322: ...Connection diagrams 10 CONNECTION DIAGRAMS 322 Ref 2003 QC PDS HARDWARE 322 This page intentionally left blank...
Страница 366: ...12 COMMERCIAL MODELS Commercial models Ref 2003 QC PDS HARDWARE 366...
Страница 367: ...ANNEXES...
Страница 368: ...ANNEX A1...
Страница 383: ...ANNEX A2...
Страница 398: ...ANNEX A3...
Страница 418: ......
Страница 419: ......