Selection criteria
5.
S
E
LECT
ING CRI
T
ERIA
Se
lecting
the
main
p
ower
supp
ly
· 194 ·
198
Ref.2003
QC-PDS
HARDWARE
NON-FAGOR asynchronous spindle motor
For NON-FAGOR asynchronous spindle motors (e.g. a high-speed spindle)
the previous tables will generally not provide all data for standard FAGOR
motors.
To properly calculate the power demanded by the NON-FAGOR
asynchronous spindle from the power supply, it is necessary to:
To know the maximum power to be provided at the axis. Always use the
mechanical power for cycles S1 or S6-40% (depending on the duty
cycle of the applicaton).
Obtain the power at the motor terminals by dividing the previous value
by the efficiency of the motor.
If the value of the motor efficiency is unknown, apply the following rule. For:
Divide the result by the efficiency of the drive.
T. H5/17
Required power drawn from the main power supply by the QC-PDS system when using a FM7
asynchronous spindle motor. HS3.
In star
Asynchronous
spindle motor
Power (kW)
(%)
Drive power
Drive for
asynchronous
spindle motor
Drive
Pm
S1
S6-40%
S1
S6-40%
(kW)
(%)
(kW)
FM7-D075
7.5
11.0
86.5
84.6
12.7
QC-DR-040
90
14.1
FM7-D110
11.0
15.5
90.2
89.2
17.4
QC-DR-055
90
19.3
FM7-D185
18.5
26.0
91.8
91.5
28.4
QC-DR-080
90
31.6
FM7-D220
22.0
33.0
89.2
88.1
37.5
QC-DR-120
90
41.6
FM7 ASYNCHRONOUS SPINDLE MOTORS HS3
Maximum power consumed by the main power supply (kW)
AS
YNC
HRONOUS
Asynchronous for spindle
Pm
1
2
POWER SUM
(kW)
2
Pm:
Required power drawn for the asynchronous spindle drive in S6-40% cycles.
This data includes the internal losses of the drive. fc: 4 kHz.
In triangle
Asynchronous
spindle motor
Power (kW)
(%)
Drive power
Drive for
asynchronous
spindle motor
Drive
Pm
S1
S6-40%
S1
S6-40%
(kW)
(%)
(kW)
FM7-D075
7.5
13.0
86.5
84.6
15.4
QC-DR-040
90
17.1
FM7-D110
11.0
20.0
90.2
89.2
22.4
QC-DR-055
90
24.9
FM7-D185
18.5
32.0
91.8
91.5
35.0
QC-DR-080
90
38.9
FM7-D220
22.0
40.0
89.2
88.1
45.4
QC-DR-120
90
50.4
where:
Pm
. Maximum power that the drive may demand from the main power supply for each motor-drive
combination. It includes the power dissipated by the drive itself. Units: kW.
NOTE.
NEVER use the peak power.
P
22 kW motor efficiency = 85 % (
= 0.85)
P > 22 kW motor efficiency = 90 % (
= 0.90)
drive efficiency = 90 % (
= 0.90)
Содержание QC-PDS
Страница 1: ...DRIVE QC PDS Hardware manual Ref 2003...
Страница 6: ...6 I 6 Ref 2003 6 QC PDS HARDWARE This page intentionally left blank...
Страница 16: ...16 Ref 2003 16 Previous I QC PDS HARDWARE This page intentionally left blank...
Страница 18: ...18 Ref 2003 18 Previous II QC PDS HARDWARE This page intentionally left blank...
Страница 80: ...2 POWER SUPPLIES Power supplies 80 Ref 2003 QC PDS HARDWARE...
Страница 138: ...3 DRIVES Drives 138 Ref 2003 QC PDS HARDWARE...
Страница 174: ...4 AUXILIARY MODULES Auxiliary modules Ref 2003 174 QC PDS HARDWARE...
Страница 302: ...8 INSTALLATION Installation Ref 2003 302 QC PDS HARDWARE...
Страница 322: ...Connection diagrams 10 CONNECTION DIAGRAMS 322 Ref 2003 QC PDS HARDWARE 322 This page intentionally left blank...
Страница 366: ...12 COMMERCIAL MODELS Commercial models Ref 2003 QC PDS HARDWARE 366...
Страница 367: ...ANNEXES...
Страница 368: ...ANNEX A1...
Страница 383: ...ANNEX A2...
Страница 398: ...ANNEX A3...
Страница 418: ......
Страница 419: ......