NC-200 PB - Installation Manual - Page: 37
PAR03
External multiplying factor (EX E type) when using linear encoders
with distance-coded reference marks and TTL feedback signals.
Independent for each axis.
Options: 1, 5, 10, 20, 25, 50.
Factory setting: 1
These values are selected by pressing
For example:
For
standard Fagor linear encoders
with squarewave signals (without
"
O
" or "
P
") e.g.: MX, CT, CX, etc. it must be set to "
1
".
For
Fagor linear encoders with squarewave signals and distance-
coded reference marks
(models with "
O
"), eg.: MOX, COX, etc.
it must be set to "
5
".
For
Fagor linear encoders with squarewave signals and distance-
coded reference marks
(models with "
O
") and 0.5µm resolution,
eg.: MOY, COY, etc. it must be set to "
10
".
PAR05
Resolution (PAR01) correction factor.
It may be used for adapting any resolution, even fractional, when
the encoder is affected by a mechanical gear reduction.
PAR08
Feedback alarm enable. On if = 1 and Off if = 0.
Digit
3
Detects the feedback alarm provided by the encoder through pins
7 and 8.
Fagor models DO NOT provide this signal.
rest
Not being used at this time. They must be set to "0".