
SEPARIX-C/-T and SEPARIX-Control CT
Page 20/37
3
Normally, the measuring transducer triggers an alarm whenever the interface sensor is in air/light
fluid, or whenever the level sensor is in fluid. For custom applications, measuring transducer config-
uration settings make it possible to invert the alarm triggering so that an alarm is triggered
whenever the interface sensor is in water or the high-level sensor is in air. In cases of doubt, check
whether the measuring transducer has been configured correctly for the application concerned.
6
List of figures
7
List of tables
Содержание SEPARIX-C L Plus
Страница 25: ......
Страница 26: ......
Страница 29: ......
Страница 30: ......
Страница 31: ......
Страница 32: ......
Страница 36: ......
Страница 37: ......
Страница 38: ......
Страница 41: ...Blank Page...
Страница 42: ...Blank Page...
Страница 43: ...Blank Page...