Electrical connection
5
Electrical connection
For the wiring of the level sensor, you need a two
-
core unshielded cable, which is termi-
nated inside the sensor head of the level sensor.
It is essential that the correct cross section be selected: the supply voltage at the level se
n-
sor must not fall below 8
V in the event of maximum current consumption (21.5
mA).
To connect the level sensor (see Figure 4):
(1)
Unscrew cap (1) using an open
-
ended spanner (SW 19)
(2)
Loosen union nut (2) of screwed cable gland (3)
Figure
4
: Connecting the CONDURIX level sensor
(3)
Feed two
-
core cable (4) through union nut (2) and fit screwed cable gland (3)
and then retighten the union nut.
(4)
Connect the two
-
core cable (4) to the screw terminals on the sensor head
mar
ked (+) and (
–
).
Pinout of the M12 plug
-
in connection:
Pin
1 =
brown
(+) Pin
3 = blue
(
-
)
(5)
Screw on cap (1)
5