Installation manual Vaska

 

10 < 

<

 

<

 

For an extensive maintenance instruction 
"maintenance protocol gas fires" see: 

 

 

10

 

Conversion to other gas type 

This can only be done by replacing the burner. To 
do so, please contact your dealer. Always provide 
the type and serial number of the appliance when 
ordering. 
 

11

 

Flue calculation 

A simple way to calculate whether the exhaust 
configuration is possible in combination with your 
fireplace, use the “Faber Flue App V2”: 

 
 
 
 

This is available free of charge and can be 
downloaded via: 

 

Internet: 
Android and PC (Windows Store, (Windows 10)). 
App Store:  
iPhone, iPad and Mac. 
Google Play: 
Android smart phones and Android tablets. 

 

Alternatively, you can use the calculation sheet 
(see chapter 13). 

 

The options for flue lengths and any flue restrictors 
are defined in a restrictor table, see 11.1. Start 
Length (STL), Total Vertical Height (TVH) and Total 
Horizontal Length (THL) are used in the table. 

 

 

Start length (STL): 

The first part that is placed on the 
fireplace and represents a certain value 
(fig. 12.1, 12.2 and 12.3 A, N and F). You 
can find this value in the upper row of the 
restrictor table. 

 

 

Total Vertical Height (TVH): 

TVH is the height difference measured 
from the top of the appliance to the 
outlet. This can be measured or 
determined in the building plan. For 
clarification, see also the TVH indication in 
the drawings (fig. 12.1, 12.2 and 12.3). 

 

 

Total Horizontal Length (THL): 

THL is the Total Horizontal Length and 
consists of elbows and pipes entirely in 
the horizontal plane. See elbows I, K and Q 
and the elements H, J, L, M, P and R  
(fig. 12.1 and 12.2). 

 

 

Horizontal length: 

The Horizontal Length consists of the 
elements H, J, L, M, P and R  
(fig. 12.1 and 12.2). 

 

 

Elbows 90° in the horizontal plane: 

Horizontal elbows are elbows entirely in 
the horizontal plane 
(fig. 12.1, 12.2 and 12.3 I, K and Q). 

 

 

Elbows 45° or 30° in the horizontal plane. 

Horizontal elbows are elbows entirely in 
the horizontal plane. 

 

 

Elbows 90° vertical to horizontal:  

These are 90° elbows, which proceed from 
horizontal to vertical (fig. 12.2 and 12.3 G, 
O and S). 

 

 

Elbows 45° or 30° vertical to horizontal 
plane: 

These are 30° or 45° elbows vertically 
offset less than 45° (fig. 12.1 B and D). 

 

 

Pipes at an angle of inclination: 

These are pipes vertically ascending at an 
angle of 30° or 45° (fig. 12.1 C). Fill in only 
in combination with at least two 30° or 
45° elbows in the vertical part. 

 

 

Restrictor table: 

See restrictor table for the correct vertical 
(TVH) and horizontal length (THL). 

 

In case of an “X” or if the values are outside the 
restrictor table, the combination is not permitted. 
Then adjust TVH or THL. 
If a value is indicated, check that the calculated STL 
value is not lower than indicated in the restrictor 
table. In this case STL must be adjusted. 
 
The value found indicates the width of the flue 
restrictor to be placed (“0” means no flue 
restrictor). Generally a 30mm flue restrictor is 
installed (fig. 1.5). 

 

Содержание Vaska

Страница 1: ...Installation manual Vaska ENG 40010627 2011...

Страница 2: ...Installation manual Vaska 1...

Страница 3: ...Installation manual Vaska 2...

Страница 4: ...Installation manual Vaska 3 1 0 1 1 1 2a 1 2b...

Страница 5: ...Installation manual Vaska 4 1 3a 1 3b 1 3c 1 4...

Страница 6: ...Installation manual Vaska 5 1 5...

Страница 7: ...ble to always install a screen for the fireplace if children elderly or disabled people are present in the same room as the fireplace If regularly vulnerable persons can be present in the room without...

Страница 8: ...91 existing chimney For an existing chimney use a Faber chimney outlet with a diameter of 100 150mm In this case the existing chimney acts as air inlet an inserted flexible stainless steel pipe discha...

Страница 9: ...nce Horizontal sections should be installed to allow a slope towards the appliance 3 degrees Built the system from the appliance If this is not possible you can make use of an adjustable flue pipe For...

Страница 10: ...of blue flames That the correct flue restrictor is fitted see fig 1 5 The outlet o Wall terminal has the correct position and side up o Roof terminal has the correct position If the maximum lengths o...

Страница 11: ...awings fig 12 1 12 2 and 12 3 Total Horizontal Length THL THL is the Total Horizontal Length and consists of elbows and pipes entirely in the horizontal plane See elbows I K and Q and the elements H J...

Страница 12: ...0 00 50 00 50 00 40 00 30 00 x x x x 12 65 00 65 00 60 00 60 00 50 00 40 00 30 00 x x x x 13 65 00 65 00 60 00 60 00 50 00 40 00 30 00 x x x x 14 65 00 65 00 60 00 60 00 50 00 40 00 30 00 x x x x 15 6...

Страница 13: ...Installation manual Vaska 12 12 Examples flue materials...

Страница 14: ...length 2m or more 2 Bend 90 0 1 Bend 45 30 or 15 0 2 Roof terminal 1 Wall terminal 0 Total Vertical Height TVH measured height rounded value meter meter Total Horizontal Length THL Calculation Part n...

Страница 15: ...lation is not possible Solution Change the TVH or THL Results Restrictor size Value for the comma mm Extra information Value behind the comma mark Install the air restrictor plate see installation man...

Страница 16: ...ficiency index EEI 88 88 88 Type heating output control room temperature no no no no yes no Diameter outlet inlet 100 150 Technical data UK and Ierland Type indication s Vaska Type appliance C11 C31 C...

Страница 17: ...outlet Distance mm D Under a gutter 500 E Under a roof edge 500 F Under a carport or balcony 500 G Vertical downpipe 300 H Inside and outside corners 500 J From wall surface to a wall outlet 1000 K Tw...

Страница 18: ...Installation manual Vaska 17 16 Troubleshooting guide...

Страница 19: ...Installation manual Vaska 18...

Страница 20: ...Installation manual Vaska 19 17 Dimensional drawings 17 1 Vaska...

Страница 21: ...Installation manual Vaska 20 17 2 Position gas connection...

Страница 22: ...Installation manual Vaska 21 18 Decoration instruction card...

Страница 23: ...Installation manual Vaska 22...

Страница 24: ...www faberfires com contact faberfires com Saturnus 8 NL 8448 CC Heerenveen Postbus 219 NL 8440 AE Heerenveen...

Отзывы: