background image

 
 
 
 

Setting the Standard in Mobile Power 

 
 

 
 

 

 
 
 

Instruction Manual for Model 

HYDRO  

300XR

 

Hydraulic Generator 

 
 
 
 
 
 
 
 
 

 

 
 
 
 

Manufacturing of: Vehicle Mounted Generators • Hydraulic Generators  

 

P.O. Box

 

582 • Chester, NY 10918 • 845-469-9151 • Fax: 845-469-7871 • Web Site/E-mail: www.fabcopower.com

  

Содержание HYDRO 300XR

Страница 1: ...le Power Instruction Manual for Model HYDRO 300XR Hydraulic Generator Manufacturing of Vehicle Mounted Generators Hydraulic Generators P O Box 582 Chester NY 10918 845 469 9151 Fax 845 469 7871 Web Si...

Страница 2: ...TOR STARTING 300 SURGE VOLTAGE REGULATOR INHERENT OUTPUT 3000 WATTS CONTINUOUS 4000 WATTS PEAK AT 100 F OIL TEMPERATURE HYDRAULIC MOTOR GEAR TYPE WITH BUILT IN FLOW CONTROL FLOW CONTROL PRESSURE COMPE...

Страница 3: ...back pressure can be caused by spikes sent back through the return from other equipment on a common return line Another potential problem can develop if several pieces of equipment are connected to o...

Страница 4: ...cal load on the generator By using this setting you will have approximately 60HZ cycles or 3600 RPM when you are running at full rated load One way this can be accomplished is by using a Photo Tachome...

Страница 5: ...what the load Drive motor speed control systems generally have a small drop in speed between no load and loaded conditions We therefore recommend setting no load speed 3 4 above nominal speed CHECKING...

Страница 6: ...GENERATOR FRAME USE GREEN WIRE FOR GROUND IF USING GFCI OUTLETS 120 TERMINAL BLOCK TERMINAL BLOCK 30 AMP OVERLOAD SELF RE SETTING 120 240 VOLT OPERATION 25 AMP OVERLOAD SELF RE SETTING GROUND SCREW O...

Страница 7: ...Pump Mount 21 572066 Coupling 24mm 22 572067 Spider 23 572068 Coupling 24 572173 Motor w Flow Control 8 gpm 25 572128 Rails 26 572154 Mounts 27 572245 Flow Control Cartridge 8 GPM restrictive 28 57226...

Страница 8: ...lace LOW NO LOAD VOLTAGE 1 Speed too low 2 Faulty rotary diodes 3 Breakdown in windings 4 Capacitor with high capacity 1 Check and adjust RPM s 2 Check and replace 3 Check winding resistance as per ta...

Страница 9: ...INE FILTER 8 OIL COOLER 9 HYDRAULIC FLUID RESERVOIR Some units may be equipped with integral priority flow control refer to specific model number External case drain line may be required on some units...

Страница 10: ...Fabco Power Instruction Manual Page 10 BRUSHLESS GENERATOR WIRING...

Страница 11: ...Fabco Power Instruction Manual Page 11 HYDRAULIC MOTOR HOSE HOOK UP Fabco Power...

Страница 12: ...Fabco Power Instruction Manual Page 12...

Страница 13: ...Fabco Power Instruction Manual Page 13...

Отзывы: