E124S 21
532434 - Rev.A
Tr
ansla
tion of the orig
inal instruc
tions
ENGLISH
6.3
SETUP
The
SET-UP
procedure consists of a series of move-
ments during which the board acquires the length
of travel and other leaf parameters. The
SETUP
procedure also registers the BUS 2easy devices that
are present.
The system needs to be carried out:
-
when
S0
flashes on the display (e.g. when the
automation is first put into operation)
-
after a board has been replaced
-
if you wish to modify the length of travel of the
leaves
-
if there are active errors that require the
SETUP
procedure to be carried out
-
if programming functions are modified that require
a new
SETUP
Checks prior to
SETUP:
-
the automation must not be set to manual mode
-
the STOP input, if not used, must be bridged
-
make sure that the settings of the following func-
tions in Basic Programming are correct:
cF
type of automation
Mn
number of motors
En
encoder (has to be enabled in order to oper-
ate)
!
While the
SETUP
procedure is being carried out, prevent
transit in the area of movement of the leaves because
the safety devices are disabled.
1. Go to the
tl
function in basic programming. The
value displayed is
--
.
The leaves must be closed. To close them now,
press the
++
button for Leaf1 and the
--
button
for Leaf2.
2. Press the
++
and
--
buttons simultaneously for a
few seconds.
The display flashes, then the first movement starts
and
S1
appears on the display.
Release the buttons.
3.
SETUP
starts. The display indicates the current
phases with a flashing code (from
S1
to
S6
, see
SETUP
phases).
If the
SETUP
procedure doesn’t start or stops before it
has been completed, the board exits from program-
ming mode and
S0
flashes on the display: check the
ERRORS that are present (Chapter § Diagnostics).
4
SETUP
phases
Display Phase
S1
Leaf1 opens slowly:
searching for the OPEN position
S2
*
Leaf2 opens slowly:
searching for the OPEN position
S3
*
Leaf2 closes slowly:
searching for the CLOSED position
S4
Leaf1 closes slowly:
searching for the CLOSED position
S5
The leaves open
S6
The leaves close
00
SETUP
has been completed. The board exits from
programming mode and the display shows the automa-
tion status - closed
* phase NOT carried out in the case of a single leaf automation.
In phases
S1
to
S4
the OPEN / CLOSED position is
recognised automatically or requires the OPEN A com-
mand, according to the configuration of the system:
■
Operation with encoder
The board automatically recognises the OPEN /
CLOSED position if a mechanical stop is present.
If there is no mechanical stop, an OPEN A command
is sent at the point in which you want the leaf to stop.
■
Operation with limit switches (with or without encoder)
If the limit switch is programmed for stopping, the
board automatically recognises the OPEN / CLOSED
position as soon as the limit switch is triggered.
If the limit switch is programmed to specify the slow-
down point, it sends an OPEN A command as soon as
the leaf reaches the mechanical stop.
■
For the S800H ENC without encoder (
cF
=
08
)
The position is recognised automatically only when
the limit switch programmed as a stop.
Otherwise, an OPEN A command is sent as soon as the
leaf reaches the mechanical stop.