Instruction manual version 1 for software version 4.04
INSTRUCTION MANUAL FOR DAAB EP104 CONTROL BOARD
Programmable input 3
No.
Name
Range
Factory Setting Ref. page
P300
Channels in programmable input 3
0 - 1
1
0
Disabled
1
Enabled
P360
Control function
0-5
0
0
Disabled
1
Open
2
Close
3
Stop
4
Open/close
5
Open/stop/close
P361
Type of control signal when activated
1 - 2
1
1
Pulse (hold-to-run mode not possible)
2
Signal for as long as the input is activated
P362
Half operation
1 - 3
3
1
Half 1
2
Half 2
3
Halves 1 and 2
P363
Limited opening
0 - 1
0
0
Disabled
1
Timed opening based on the time specified in C412 and/or C414.
P370
Motor lock
0 - 1
0
0
Disabled
1
The barrier cannot be operated without a signal at programmable input 3. If the signal disappears the
barrier is stopped.
P380
Park
0 - 2
2
0
Disabled
1
Automatic closing disabled after the input is activated, reset by another control signal
2
Automatic closing disabled by a constant signal
P390
Interlock opening
0 - 1
0
0
Disabled
1
Opens the local door if P360 is set to open, and passes the signal on to the remote door
P396
Blocking disabled for local and remote doors. Only
works if there is a constant signal and P361 has the
value 2.
0 - 1
0
0
Disabled
1
Active
P398
Automatic closing disabled for remote door Only
works if there is a constant signal
0 - 1
0
0
Disabled
1
Active