![F5 VIPRION 2400 Скачать руководство пользователя страница 55](http://html1.mh-extra.com/html/f5/viprion-2400/viprion-2400_platform-manual_3088242055.webp)
AC power redundancy provisioning
The platform supports up to two AC power supplies. The power supplies are auto-ranging 100-127VAC to
200-240VAC input. Each slot is provisioned to draw up to 300W; therefore, one power supply with low-line
input can support two blades with no redundancy, or the same supply with high-line input can support up
to three blades. The following table shows some of the possible blade and power supply redundancy
configurations.
Table 1: AC power provisioning recommendations
1 + 1 redundancy
No redundancy
Supplies
(high-line)
Supplies (low-line)
Supplies
(high-line)
Supplies (low-line)
Blade quantity
2 (2800W available)
2 (2400W available)
1 (1400W available)
1 (1200W available)
1 (450W)
2 (2800W available)
2 (2400W available)
1 (1400W available)
1 (1200W available)
2 (700W)
2 (2800W available)
2 (2400W available)
1 (1400W available)
1 (2400W available)
3 (950W)
2 (2800W available)
2 (2400W available)
1 (4000W available)
1 (2400W available)
4 (1200W)
AC platform power consumption (low-line input)
The actual amount of power draw from the AC source depends on the type and number of blades, as well
as the power supply AC source voltage and redundancy configuration. The following table shows possible
configurations for low-line voltage, and the typical and maximum power draw.
Table 2: AC mains total system power draw (low-line input)
Number of power
supplies installed
Maximum system
power draw
Typical system power
draw
Blade quantity
1
365W
290W
1
1
625W
470W
2
1
885W
655W
3
1
1145W
830W
4
2
390W
320W
1
2
640W
490W
2
2
895W
670W
3
2
1150W
845W
4
55
Platform Guide: VIPRION 2400
Содержание VIPRION 2400
Страница 1: ...Platform Guide VIPRION 2400 MAN 0344 01...
Страница 2: ......
Страница 6: ...6 Table of Contents...
Страница 38: ...38 Platform Installation...
Страница 44: ...44 Platform Maintenance...
Страница 45: ...Appendix A Environmental Guidelines Topics General environmental guidelines Guidelines for AC powered equipment...
Страница 48: ...48 Environmental Guidelines...
Страница 59: ...Appendix D China RoHS Requirements Topics Hazardous Substance Levels for China...
Страница 61: ...61 Platform Guide VIPRION 2400...
Страница 62: ...62 China RoHS Requirements...
Страница 67: ...7 Place the foam cover on top of the blade box 8 Close the blade box 67 Platform Guide VIPRION 2400...
Страница 72: ...72 Index...