General purpose inputs
The ezeio
™
has four general purpose inputs. Each input may be configured
individually in one of four ways described here:
Jumper
setting
Description
The factory default setting
is
Contact, Pulse or
Resistive (0-50kOhm).
An internal 10k resistor will hold the input to 5V.
See pg. 16
0-5VDC
Input impedance is >70kOhm.
Raw reading is about 10000 at 5.0V (0.5mV per count)
See pg. 17
0-10VDC
Input impedance is >70kOhm.
Raw reading is about 10000 at 10.0V (1mV per count)
0-30mA (suitable for 4-20mA transducers)
An internal 100 Ohm resistor connects the input terminal
to Common.
Raw reading is about 10000 at 30mA (3uA per count)
See pg. 18
To access the input jumper settings, open the ezeio
™
by removing the four
black screws.
Page 15 of 121