EZ-Path EZP433W Скачать руководство пользователя страница 1

3.   Fit all pathways side by side through opening. 
4.   Slide wall plate over pathways.  With the ends of all pathways evenly aligned, set the wall plate to the correct wall thickness 

Pre position and fasten wall plate to one side of pathway (fig. 3) roughly centering pathway within barrier.  

5.   Carefully tighten all set screws (See Fig 4). 
6.  Slide plate with mounted pathways tight against wall surface. 
7.   Fasten wall plate to wall as required (See Table A), (Fig 5). 
8.   Moving to the opposite side of the wall, install remaining plate making sure to tighten all set screws.  Fasten plate to wall if required.

GENERAL - READ COMPLETELY BEFORE INSTALLING

This product allows for several optional installation methods.  

The pathway (device) consists of an enclosed heavy 

gauge galvanized steel channel with a detachable lid.  

Pathways (devices) are ordered separately.  Gang plates 

are designed to accommodate up to four or seven device 

installations.  Component requirements will vary according 

to the method of installation chosen.

NOTE: 

Wall installations require this device to be installed with 

the top (lid) facing upward.  The lid may be identified by the  

EZ-Path

®

 logo stamped onto the face of the steel lid.  Gang plates 

are asymmetrical with the stencil marking the top.

INSTALLATION SHEET

Four & Seven Gang Mounting Plates

EZP433W, EZP433GK, EZP733W, EZDP733GK

Page 1 of 2 

 

 

       Installation Sheet  

 

EZ-PATH® Four & Seven Ganga Mounting Plates                                               

ZIS1005 - 3345

ZIS1005 - 3345

TABLE A:  Slot Size & Capacity

Stud spacing

16” (406 mm)

24” (610 mm)

Mounting plate 

part number

EZP433W

EZP733W

Capacity

(Qty. of devices)

(4) EZD33FWS

(7) EZD33FWS

Slot size

12-1/8” x 3-1/8”

(308 mm x 80 mm)

21-1/8” x 3-1/8”

(537 mm x 80 mm)

Fastener Requirements

Gypsum board

2” (51 mm) L Type S screws

2” (51 mm) L Type S screws

Fasten to studs

(OPTIONAL)

(REQUIRED)

Masonry

1” X 1/8”masonry screws

(25 mm x 3 mm)

(OPTIONAL)

1” X 1/8”masonry screws

(25 mm x 3 mm)

(OPTIONAL)

Option 1 – Installation in Finished Walls

1.  Determine a suitable location for installation. Plates are 

designed to allow either 4 pathways (studs 16” , 406 mm OC) 

or 7 pathways (studs 24”, 610 mm OC) to be installed hori-

zontally in a row. Installation requires an opening to be cut or 

formed completely through the wall (both sides) per the dimen- 

sions listed in Table A. In hollow walls, care must be exer-

cised to assure that slots on both sides are properly aligned 

(See Fig. 1).

2.  Install gasket  tape to the flat side of both plates (See Fig 2).   

Apply by aligning tape to the inside edge of the framed 

opening.  Remove release liner and adhere tape. 

Option 2 – Installing Devices Prior to Wallboard (New Wall Construction)

1.  Invert gang plates such that flanges project into stud cavity and fasten directly to studs using four 5/8” (16 mm) Type S 

screws on each side of stud cavity (See Fig. 6).

2.  Install devices and tighten set screws provided with device using Allen wrench supplied (See Fig. 3 & 4).

3.  Complete wall construction as required by design.  Opening in wallboard facing shall be cut so that clearance between 

devices and wallboard does not exceed 1/8” (3 mm).

4.  Resulting gap shall be filled with joint compound or SpecSeal

®

 brand firestop sealant at the option of the installer (See Fig. 7 & 8).

Fig. 1

Fig. 2

Fig. 3

Fig. 5

Fig. 4

Fig. 7

Fig. 8

Fig. 6

Отзывы: