Stop the stopwatch when the purging indicator stops flashing.

Check stopwatch timing to verify that the actual purge time is equal to or greater than the required purge time.

Note: The recorded purge time must never be less than the required purge time.

The system is now operating correctly in leakage compensation mode.

If the system has not performed as expected, check the installation thoroughly and ensure it has been carried 
out according to the instructions.

If an obvious problem has not been highlighted and corrected, follow the procedures in the 

Fault Finding

 

section.

If all checks have been carried out and the system still does not perform as expected, contact your local 
distributor or Expo Technologies.

Section 3: Application Suitability

MiniPurge

®

 systems are certified for use in hazardous locations, where the hazardous location is non-mining 

(above ground) and the hazard is caused by flammable gasses, vapours or dust. Depending on the model the 
systems may be used in IECEx and ATEX Zone 1(21) and/or Zone 2(22) - Categories 2 and 3 respectively.

MiniPurge

®

 systems may be used for hazards of any gas group. Apparatus associated with the MiniPurge

®

 

system, such as intrinsically safe signalling circuits and flameproof enclosures containing switching devices 
may be limited in their gas group. The certification documentation supplied with any such devices must be 
checked to ensure their suitability.

This system is primarily designed for use with compressed air. Where other inert compressed gasses are 
used (Nitrogen, for example) the user must take suitable precautions so that the build up of the inert gas does 
not present a hazard to health. Consult the Control of Substances Hazardous to Health (COSHH) data sheet 
for the gas used. Where a risk of asphyxiation exists, a warning label must be fitted to the pressurized 
enclosure.

The following materials are used in the construction of MiniPurge

®

 systems. If substances that will adversely 

affect any of these materials are present in the surrounding environment, please consult Expo Technologies 
for further guidance.

Indicator

Colour

Status

Alarm / Pressurized

Green 

Pressurized and in leakage compensation mode

Purging

Black  

No longer in purge mode

Materials of Construction
Stainless Steel

Aluminium

Acrylic

Mild (Carbon) Steel

Nylon

Silicone

Brass

Polyurethane

Neoprene

ABS

Polycarbonate

Polyester (glass filled)

Содержание MiniPurge D808/ET

Страница 1: ...these instructions Please refer to the standard for principles and definition These instructions apply only to the pressurizing system it is the responsibility of the manufacturer of the pressurized e...

Страница 2: ......

Страница 3: ...on of the System 10 Relief Valve Unit 10 Air Supply Quality 10 Pipe Work 11 Multiple Enclosures 11 Provision and Installation of Alarm Devices 11 Power Supplies and their Isolation 11 Power Interlock...

Страница 4: ...Db Tamb 20 C to 55 C IECEx SIR07 0027X Ex pxb ia IIC T5 Gb Ex pxb ia IIIC T100 C Db Tamb 20 C to 55 C PA Power and Alarm Switches Integral PA Terminal Box OV Purge Outlet Valve is pneumatically opera...

Страница 5: ...female Minimum supply line 50 mm 2 I D Pipe Reference points signals 1 8 NPT female Visual Indicators Alarm Red Pressurized Green System Purging 4 LEDs that flash sequentially to indicate elapsed tim...

Страница 6: ...ermediate and CLAPS sensor calibration point For example Minimum pressure 5 mbarg intermediate pressure 6 5 mbarg CLAPS sensor 9 mbarg Purge Time User selectable in 1 minute intervals up to 99 minutes...

Страница 7: ...in air supply pressure during the purge process Operation of the System Once the system is installed correctly turn on the air supply Refer to Commissioning section The purge system commences the purg...

Страница 8: ...be used in IECEx and ATEX Zone 1 21 and or Zone 2 22 Categories 2 and 3 respectively MiniPurge systems may be used for hazards of any gas group Apparatus associated with the MiniPurge system such as i...

Страница 9: ...he enclosure before pressurization Purging is the process of removal contaminated air and replacement with air or inert gas known to be free from flammable gas The duration of this purge process is no...

Страница 10: ...is is the regulator that controls the leakage compensation air flow into the enclosure after the purging is complete It either increases or decreases the air flow into the enclosure as appropriate to...

Страница 11: ...ioning section Alarm Only Circuit AO If the pressure in the pressurized enclosure is too low the system will normally cut off electrical power to it In certain circumstances where local codes of pract...

Страница 12: ...d enclosure Purge air passes through the Relief Valve Unit the preset pressure differential across the appropriate orifice ensures that the purge flow sensor is activated once the selected purge flow...

Страница 13: ...s might affect the calibration of the device In particular the exterior of the spark arrestor should not be painted or blocked in any way Air Supply Quality The MiniPurge system should be connected to...

Страница 14: ...its associated terminal boxes Provision and Installation of Alarm Devices When the pressure inside the pressurized enclosure is above the minimum the Minimum Pressure Sensor returns a positive pressu...

Страница 15: ...ior to commissioning check that the Ex e terminal box is clean the connections have been made properly the cables laid correctly and all screws in the terminals are secure In all cases the application...

Страница 16: ...CLAPS regulator clockwise till the Low Pressure Alarm Indicator turns green This activates the Purge Flow Regulator Slowly open the Purge Flow Regulator until the Pressure Relief Valve opens This is...

Страница 17: ...ssure Sensor check readings on manometer as system will automatically re purge when it reaches minimum pressure 19 While the system re purges return the CLAPS Regulator to the initial setting 20 If th...

Страница 18: ...table for use in the hazardous location There are no unauthorised modifications The air supply is uncontaminated The interlocks and alarms function correctly Approval labels are legible and undamaged...

Страница 19: ...check the correct setting of the relief valve after adjustment The adjustment is sensitive and it is recommended that a 1 4 turn maximum adjustments are applied between tests Re calibration of the Pr...

Страница 20: ...designed for ease of fault finding and many of the components fitted are plug in or chassis mounted Check components by substitution only after establishing that such action is necessary Before carry...

Страница 21: ...in the supply pipe Static pressure of 5 barg must be maintained during purge Check air supply pressure at the inlet to the control unit Ensure that the supply pipe bore is suitable for the flow rate P...

Страница 22: ...e factory set to the value as stated on the Customer Test and Inspection Sheet S0015 018 Pressure gauge Air Supply Pressure 0 10 barg S0015 135 Miniature gauge Logic Pressure 0 4 barg ETM IS31 001 IS...

Страница 23: ...om downloads or refer to ML497 Component Certificate Number Purge System ATEX Certificate SIRA 01ATEX1295X IECEx Certificate IECEx SIR07 0027X INMETRO T V Certificate T V 12 1462X MIU e Ex e Terminal...

Страница 24: ...t i m i L s e i g o l o n h c e T o p x E n o i t c u d o r p B D 5 6 1 W T Y E R R U S M O D G N I K D E T I N U E L G N A d r 3 N O I T C E J O R P S U T A T S G N I W A R D E T A D N W A R D m m N...

Страница 25: ...U S S E R P W O L E T A I D E M R E T N I 8 N E E R G D E R R O T A C I D N I P I R T M R A L A E R U S S E R P W O L 9 N E E R G D E R R O T A C I D N I M R A L A E R U S S E R P W O L E T A I D E M...

Страница 26: ...7 6 6 5 7 2 6 6 1 8 S E T O N E B T S U M E V L A V F E I L E R E H T N W O H S E D U T I T T A E H T N I D E T N U O M b l 1 5 g k 3 2 X O R P P A S I T H G I E W 0 0 1 8 0 0 2 V R A S I E D O C T R...

Страница 27: ...HG DV FRQILGHQWLDO DQG DUH UHWXUQDEOH XSRQ UHTXHVW 7KH DUH QRW WR EH FRSLHG RU FRPPXQLFDWHG LQ SDUW RU LQ ZKROH ZLWKRXW ZULWWHQ FRQVHQW IURP SR 7HFKQRORJLHV LPLWHG QHLWKHU DUH WKH WR EH XVHG LQ DQ ZD...

Страница 28: ...EET No OF SURREY TW16 5DB UNITED KINGDOM DRAWING No SCALE The contents of this drawing document are Copyright Expo Technologies Limited They are to be treated as confidential and are returnable upon r...

Страница 29: ...ORMALLY PLUGGED FLATNESS TO BE LESS THAN 0 4mm OVER ANY 100mm LENGTH UNSPECIFIED TOLERANCES MATERIAL DR WN APP D CHK D DRAWING STATUS APPROVED MOD No DATE ISSUE 3rd ANGLE PROJECTION DIMENSIONS IN mm D...

Страница 30: ...OWN BLACK ALARM PRESSURIZED MOTOR ENCLOSURE PRESSURE BULKHEAD PURGE OUTLET OPEN SIGNAL 2 PURGE INDICATOR YELLOW PURGING ELECTRONIC TIMER TIMER SWITCH PURGE COMPLETE VALVE OR GATE TIMER VALVE INTERMEDI...

Страница 31: ...UH WKHUHIRUH H FOXGHG IURP WKH RZ 9ROWDJH LUHFWLYH 3UHVVXUH TXLSPHQW LUHFWLYH 8 0LQL3XUJH 6 VWHPV DUH FODVVLILHG DV QRW KLJKHU WKDQ FDWHJRU XQGHU UWLFOH RI WKLV LUHFWLYH DQG LQWHQGHG IRU XVH LQ SRWHQW...

Страница 32: ...This Page Intentionally Left Blank...

Страница 33: ...This Page Intentionally Left Blank...

Страница 34: ...This Page Intentionally Left Blank...

Страница 35: ...This Page Intentionally Left Blank...

Страница 36: ...Technologies UK Expo Technologies Ltd Unit 2 The Summit Hanworth Road Sunbury On Thames TW16 5DB UK T 44 20 8398 8011 F 44 20 8398 8014 E sales expoworldwide com Expo Technologies China Qingdao Expo...

Отзывы: