Tritex 1 Installation and Setup
92
09/27/12
PN: 27666
Exlar Corporation
Rev. M
952-500-6200M
Analog Input Scaling
The analog input can be configured for either voltage mode (0- 10V) or current mode (0-20 mA).
Analog input scaling is provided to allow scaling the actual available analog input range to the
range of the drive’s analog inputs range. These minimum & maximum values will correspond to
the Minimum and Maximum commanded Position, Velocity or Currents on the corresponding
Analog Position, Velocity & Torque pages.
On line scaling:
When on line with the drive the scaling can be set automatically by the drive.
First apply the minimum analog input (4mA for example) and activate the Minimum Set to Input
Value button. Next apply maximum analog input (20mA for example) and activate the Maximum
Set to Input Value button.
A download must be performed to save the values in the drives non-volatile memory.
Содержание Tritex
Страница 27: ...Tritex 1 Installation and Setup 27 09 27 12 PN 27666 Exlar Corporation Rev M 952 500 6200M TLM20 Dimensions...
Страница 28: ...Tritex 1 Installation and Setup 28 09 27 12 PN 27666 Exlar Corporation Rev M 952 500 6200M TSM20 Dimensions...
Страница 29: ...Tritex 1 Installation and Setup 29 09 27 12 PN 27666 Exlar Corporation Rev M 952 500 6200M TLM30 Dimensions...
Страница 30: ...Tritex 1 Installation and Setup 30 09 27 12 PN 27666 Exlar Corporation Rev M 952 500 6200M TSM30 Dimensions...
Страница 122: ...Tritex 1 Installation and Setup 122 09 27 12 PN 27666 Exlar Corporation Rev M 952 500 6200M TTPS1048 Dimensions...
Страница 125: ...Tritex 1 Installation and Setup 125 09 27 12 PN 27666 Exlar Corporation Rev M 952 500 6200M T232485 Schematic...
Страница 132: ...Tritex 1 Installation and Setup 132 09 27 12 PN 27666 Exlar Corporation Rev M 952 500 6200M TTSR1 Dimensions...
Страница 134: ...Tritex 1 Installation and Setup 134 09 27 12 PN 27666 Exlar Corporation Rev M 952 500 6200M Declaration of Conformity...