Tritex 1 Installation and Setup
50
09/27/12
PN: 27666
Exlar Corporation
Rev. M
952-500-6200M
Analog Input
An analog input is provided for use as a position, velocity or current command. The input can be
configured to operate using a 0-10 VDC signal, or using a 0-20ma current signal.
(See software section for configuration of the analog input and analog positioning parameters.)
Analog input wiring from voltage or current control external controller
Note: Analog input reference from an external controller must be referenced to single point
ground to prevent damage to the analog input circuit.
Internal Analog Input Circuit
Analog in +
+
-
Analog in -
Current Mode
Selector
500Ω
20kΩ
20kΩ
+
-
+
VDC
-
Single Point
Panel
Ground
External Controller
Analog in +
Analog in -
Internal
100 Ohms
GND
Ground on Power
Connector
Single Point
Panel
Ground
Tritex
Содержание Tritex
Страница 27: ...Tritex 1 Installation and Setup 27 09 27 12 PN 27666 Exlar Corporation Rev M 952 500 6200M TLM20 Dimensions...
Страница 28: ...Tritex 1 Installation and Setup 28 09 27 12 PN 27666 Exlar Corporation Rev M 952 500 6200M TSM20 Dimensions...
Страница 29: ...Tritex 1 Installation and Setup 29 09 27 12 PN 27666 Exlar Corporation Rev M 952 500 6200M TLM30 Dimensions...
Страница 30: ...Tritex 1 Installation and Setup 30 09 27 12 PN 27666 Exlar Corporation Rev M 952 500 6200M TSM30 Dimensions...
Страница 122: ...Tritex 1 Installation and Setup 122 09 27 12 PN 27666 Exlar Corporation Rev M 952 500 6200M TTPS1048 Dimensions...
Страница 125: ...Tritex 1 Installation and Setup 125 09 27 12 PN 27666 Exlar Corporation Rev M 952 500 6200M T232485 Schematic...
Страница 132: ...Tritex 1 Installation and Setup 132 09 27 12 PN 27666 Exlar Corporation Rev M 952 500 6200M TTSR1 Dimensions...
Страница 134: ...Tritex 1 Installation and Setup 134 09 27 12 PN 27666 Exlar Corporation Rev M 952 500 6200M Declaration of Conformity...