4.1.7 Temperature sensor correction
Service menu
Temperature sensor correction
Description
Settings for sensor correction/calibration
For correction of measurement errors, cable resistance
and sensor tolerances.
Submenu
Any comments
Shown if
heating coil
1
is configured
Calibrate temperature measurement - Heating coil 1
Set sensor offset [+/-3.5°C]
●
Shows current sensor temperature [°C]
●
Set calibration value [°C]
Shown if
heating coil
2
is configured
Calibrate temperature measurement - Heating coil 2
Set sensor offset [+/-3.5°C]
●
Shows current sensor temperature [°C]
●
Set calibration value [°C]
Shown if
water cool-
ing
is configured
Calibrates temperature measurement - Water cooling
Set sensor offset [+/-3.5°C]
●
Shows current sensor temperature [°C]
●
Set calibration value [°C]
Shown if
outdoor sen-
sor
is configured
Calibrates temperature measurement - outdoor tem-
perature sensor
Set sensor offset [+/-3.5°C]
●
Shows current sensor temperature [°C]
●
Set calibration value [°C]
Up to 4
additional sen-
sors
can be configured
Calibrates temperature measurement - Addition sen-
sor
Set sensor offset [+/-3.5°C]
●
Shows current sensor temperature [°C]
●
Set calibration value [°C]