GB - Retrofitting of condensate tube VEX100CF Vertical
15/26
1. GB - Retrofitting of condensate tube VEX100CF Vertical
Condensation can occur in the VEX exhaust area if there is high humidity in the extract
air and the air is passing at high speed through the heat exchanger.
The Contube Kit leads this condensate to the VEX base tray.
The condensate tube passes through the outdoor air area, so icing may occur.
It is therefore recommended that frost protection is fitted, using Siphon electrical heat
tracing. (additional accessory)
The following parts
are included
:
Please note!
Frost protection with Siphon electrical heat tracing must be ordered separately.
Product number: SIPHONHE02
Disconnect power at the isolation switch before opening the VEX doors.
The work must be performed by an authorised electrician, in accordance
with locally applicable regulations and legislation.
The cover plate is situated in the plate between the supply air and the exhaust air area.
1.1 Functional description
Hose dia. 12
2.0 m
Rear drainage nozzle
1 item
Straight connector dia. 12 mm
- 1/2”
1 item
Insulated terminal pipe 0.75
mm
2
3 items
1.2 Removing the cover plate
Step
Action
Photo
1.
Remove the four rivets and sealant.
2.
Enlarge the four dia. 3.5 holes to dia. 4.5 mm
with a drill.