Diagrams
See appendix 1 for VEX200 diagrams.
Menu 2.1.1 - Set points for regulators
2.1.1 Setp. regulators
Room
Heat recovery
Cooling unit
Heating unit
Compensation:
Outdoor temp.
Summer
0,0
10,0
10,0
10,0
Inactive
Inactive
This menu shows set points for:
● Room temperature regulator
● Heat recovery regulator
● Cooling regulator
● Heating unit regulator
Compensations:
● List of compensations (active/inactive)
Menu 2.2 - Airflows
2.2 Airflows
Supply air
Supply air
Extract air
Extract air
3150l/s
11340m³/h
3225l/s
11610m³/h
The menu shows the airflows (converted to airflows at 20°C) specified in l/s and
m
3
/h. Uncertainty for the measured airflow is less than ±8%.
Menu 2.3 - Motor controller parameters (MC parameters)
2.3 MC parameters
Supply air:
Maximum
Set point
Minimum
Extract air:
Maximum
Set point
Minimum
50.0Hz
30.0Hz
14.0Hz
50.0Hz
30.0Hz
14.0Hz
FC: The menu shows maximum and minimum frequencies. The set point shows
the frequency at the current ventilation level (e.g. 30 Hz).
3005167-2022-02-02
Operation
52/108