Start configuration
Step
Action
1
Check that the correct configuration for the VEX/CX has been se-
lected at the factory via menu 3.3.
2
Check that all accessories have been configured in menu 3.4
3
If the CO
2
sensor has been mounted, check in menu 3.1.2.1 "CO
2
compensation", whether CO
2
compensation has been activated.
4
If the humidity sensor (RH sensor) has been installed, check that
humidity compensation has been activated in menu 3.1.2.2 "Hu-
midity compensation".
5
Go to menu 4.5 "Current list", and check whether any units from
the configuration menu are reporting errors. Alarm icon is shown in
the menu bar
6
If a unit is reporting an error but has been correctly configured,
check the installation.
3.3 Configuration
Type >
Size >
Fan positioning >
Direction >
Rotor type >
Cleaning zone >
200
1
Orientation
H
Right
Cond.
None
x50
Line in menu 3.3
Factory-set and
should not be
changed.
Remarks:
Type
x
Size
x
Fan location
x
Direction
Adjustable. See section se-
lecting Left/Right
Rotor type
x
Cleaning zone
x
3005167-2022-02-02
Starting up the unit for operation
17/108