UBT2000 - Digital Universal Bus Transceiver

  

 

 

 

Only suitably qualified personnel should install this equipment.

The UBT2000 expands the scope of The Ex-Or MLS Digital by enabling otherwise 
uncontrolled lighting and non-lighting loads to be brought into the system.               
UBTs also allow external devices to provide inputs into the system. 

Fixing

The UBT is supplied   in a protective   housing   which should be mounted where it is 
accessible for programming purposes.   It must not be installed in a position where it 
would be exposed to infrared pollution, e.g. in close proximity to fluorescent tubes.

Connection

2

The MLS Bus cable should be 1.5mm    twisted   pair   unscreened.

2

The digital output cable should be 1.5mm    2-core flex unscreened.

2

2

The mains supply terminals are suitable for 1 x 4mm    or 2 x 2.5mm  cable.
For connection options please see overleaf; also MLS Wiring Guide AN4001.
Do not connect mains to the MLS bus.

W4078H 

Technical Data

 

2

MLS CABLE: 1.5mm  unscreened twisted-pair : see Application Note AN4001
RANGE TO HP2000: 0.2m (8 inches)
OPERATING VOLTAGE: 230V 50Hz (UK & Europe)
PRODUCT RATING & RECOMMENDED CIRCUIT PROTECTION: 10 Amps
MAXIMUM RECOMMENDED LOAD:10 Amps

Incandescent lamps: 1500W max (at 230V)

DIGITAL DIMMING OUTPUT LOAD: up to 20 BALLASTS
POWER CONSUMPTION: <10W 
WEIGHT: 112g
SIZE: 175mm x 125mm x 75mm

 

 

  

    

     

 

This device presents a load of 1 unit to the MLS Bus.

Commissioning a UBT using the HP2000

When commissioning a UBT, the HP2000 should be held at a shorter 
distance from the unit than for detectors, ie not more than 0.2m away 
from the infrared transmitter and receiver which are positioned just 
below the MLS bus connections.

1. Switch on HP2000 by pressing the red power button.

2.   Point HP2000 at the UBT and press the DOWNLOAD button.   The 

HP2000 will confirm the product’s identity and call up the correct 
menu of parameters and their current settings.

3. Use a combination of UP, DOWN, FORWARD and BACK buttons 

to navigate the parameter menu, selecting options for each shown. 
(See Tips below.) 

4. When options for all parameters have been selected, point the 

HP2000 at the UBT and press the UPLOAD button.   The 
luminaire(s) will switch off briefly during the programming process 
and the HP2000 shows DATA OK to confirm operation.

5. After a short period of inactivity (default 5 minutes), the HP2000 

hibernates retaining the most recent settings.

Tips

i) 

Where there are only two options such as ON/OFF, a double click 
of the OK button toggles between them. 

ii)   Where there are multiple options, a double click of the OK button 

recalls a list of all options for that parameter.   Use the UP, DOWN 
and OK buttons to select.

iii)  Use the OK button to go forward (through the menus) without 

displaying help pages.

iv)   Press UPLOAD at any time to transfer all current settings from the 

handset to the product.

Please refer to HP2000 instructions for comprehensive commissioning 
details.
 

When commissioning, the following options are available (pre-sets shown in bold):

  

 

 

 

 

 

 

 

 

Function

Options

Description

Power-up

On

/Off

Sets the digital output and relay state at power-up 
irrespective of occupancy.

Response

Auto

/

Auto: switches on and off automatically. 

Semi-auto

Semi-auto: requires input commands on inputs 1-3 or the 
MLS Bus to switch on but switches off automatically.

Min on-time

No

/Yes

If set to Yes, the luminaires stay on for at least 20 minutes
regardless of the Off delay.  Once the Minimum on-time 
has elapsed, the programmed Off delay is reinstated.  

Off delay

5-60 min 

Off delays are programmable in 5 minute steps with a 

20 min

10 second walk-test option.

Bus connect

Yes

/No

Selecting No electronically disconnects the unit from the 
bus.

Zones 

1 to 50

Seven zones are listed which can be programmed at the  

Pre-set to --

time of commissioning.  Detectors programmed to the 

(no zone)

same zone switch on or stay on when movement is 
detected anywhere in that zone.  The 5th, 6th and 7th 
entries in the list may also be programmed as Common 
Zones or Global Zones (see Note 3 overleaf re Global 
Messages).

Input 1-3

Various 

When the switch inputs go active, the programmed 

Sustain

command is transmitted to the zones in the UBT’s list.

Start lamps

Min

/Max

Selects the digital dimming output at power-up which then 
adjusts to the required state.

Entry scene 1-6

Choose scene 1-6 which is selected when the area is first

Scene 1

occupied.  

Fade to off

No

/Yes

After the Off delay, digital dimming output either switches 
off or fades to off gradually over a few minutes. 

Vacant

Off

Switch off after off delay.

Scn 6

Go to Exit Scene (Scene 6) until next occupancy.

Scn 6 3 hr

Go to Exit Scene (Scene 6) for 3 hours then switch off.

Scn 6 bld

Go to Exit Scene (Scene 6) until building is vacated then
switch off.

User remote

Simulates HC5 functions.

Request

Extracts information regarding product type and current 

download

settings from Ex-Or device.

Programme all

Transmits all programme parameters.

Installation and Commissioning

Instructions

Note: HP2000 required for commissioning

(Please read these instructions fully before installation)

UBT2000

Universal Bus Transceiver for use with

The Ex-Or MLS Digital

Ex-Or Limited

 

Haydock Lane, Haydock, 
Merseyside WA11 9UJ

Tel: (01942) 719229 
Fax: (01942) 272767  
Email: [email protected]
www.ex-or.com

At the end of their useful life 
the packaging and product 
should be disposed of via a 
suitable recycling centre.
Do not dispose of with normal 
household waste.
Do not burn.

Important Additional Notes

1.

All terminals on this product are provided for final connections.   It is not intended that the product 
be used as a junction box for looping cables. 

2.

A means for disconnection must be incorporated in the fixed wiring in accordance with the 
current wiring regulations.