WARNING 230V a.c. 

The  connections  to this equipment  should be made by a  suitably 
qualified person in accordance with the current wiring regulations.

It is strongly recommended to use Ex-Or latching type connectors. 

The unit must be earthed.

Connect  UltraLite  provides  an  efficient  way  to  inter-connect  presence 
detectors and luminaires using industry standard connectors. One or two 
detectors can be connected to up to ten luminaires depending upon the 
configuration required.

Electrical Connections

Screw  terminals  are  provided  under  the  cover  for  power  supply 
connections  and  extension  of  the  dimming  control  to  other  Connect 
Boxes.  Override  switches  may  also  be  connected  here  providing  a 
means to control the switched live connections to the luminaires.

The installation should provide means of supply disconnection and over-
current  protection.  Please  refer  to  diagrams  overleaf  for  further 
information.

The cover of the cable chamber is removed by inserting the tip of a flat 
bladed screwdriver into the catch recess and exerting light pressure on 
the handle in an inboard direction while lifting the long outboard edge of 
the cover.

The cable entries, for 20mm conduit, bushes or glands are semi-pierced 
in the walls of the cable chamber and can easily be removed from the 
outside with a 20mm hole saw.

If the cables are not routed right into the box through conduit or trunking, 
a cable restraining gland must be fitted at the cable entry for strain relief.

Fixing 

The box should be sited on a suitable, smooth, flat surface using the two 
end fixing flanges. Consideration should be given to the box’s location as 
access will be required to install the plugs. The box must not be distorted 
when fixing.

Alternatively, the box may be rod-fixed. In this case, the fixing should be 
substantial enough to withstand the action of plugging and un-plugging 
connectors.

OPERATING VOLTAGE: 230V 50Hz (UK & Europe)
PRODUCT RATING/RECOMMENDED CIRCUIT PROTECTION: 16 Amps
MAXIMUM LOAD PER OUTLET: 6 Amps*
MAXIMUM TOTAL LOAD: 16 Amps*

2

 

2

SUPPLY TERMINAL CAPACITY: 6.0mm (2 x 2.5mm )

2

DIMMING TERMINAL CAPACITY: 4.0mm
CASE MATERIAL: Polycarbonate
CASE FINISH: Lightly textured light grey

Technical Data

Installation Instructions

Connect UltraLite 

Connection Centre

CDW10U2UL 

 

Factory Configuration

When  the  unit  is  shipped,  the  dimming  control  and  switched  lives  are 
linked in the terminal space. LK2 and LK3 MUST BE REMOVED if two 
detectors with dimming outputs are connected to the box. (LK1 must also 
be removed when using analogue detectors.)

A red indicator in the connection chamber indicates that power is 
present.

D

H

F

D
2

W

Height (H) = 50mm (108mm including plug and lead)
Width (W) = 315mm (361mm including mounting feet)
Depth (D) = 205mm

Dimensions

W5007A

At the end of their useful life 
the packaging and product 
should be disposed of via a 
suitable recycling centre.
Do not dispose of with normal 
household waste.
Do not burn.

Connections  are  made  as 
illustrated  to  the  left. Two  spare 
terminals  are  provided  for 
termination purposes. 

Live  (Lin)

  is  routed  to  the  two 

detector connectors (A1 and B1).

Maintained Live (ML)

 is routed 

to  the  ten  luminaire  connectors, 
A2-A6 and B2-B6.

SWA

 is the switched live output 

from a detector connected to A1.

SWB

 is the switched live output 

from a detector connected to B1.

LK1

  is  a  common  connection 

between  the  switched  live  from 
each detector position. It must be 
r e m o v e d   t o   s e p a r a t e   t h e  
luminaires into two groups.

Dimming Control Terminals

The Dimming Control signals
from each detector to its group
of luminaires are accessible at
terminals under the connection
chamber cover. Links are factory 
fitted to join the two groups on to 
one detector.

Lin

ML

MAINTAINED LIVE

Internally connected to A2-6 and B2-6

LIVE INPUT 

Internally connected to A1 and B1
Lin internally linked

MAINS INPUT: 230V 50Hz
Max load on any single outlet: 6A
Max total load: 16A
tc: 5 - 50 C
No user-serviceable parts inside

EARTH INPUT 

Protected Earth 
E terminals internally linked

GROUP A

(Connect wall switches
here if not using 
plug-in detectors)

GROUP B

Manual input OneSwitch 

Group A

(Only when used with compatible detectors) 

Manual input OneSwitch 

Group B

LK1 
External 
Link

Spare

Spare

Spare terminals have 
no internal connection

A

B

B+
A+

_
_

LK2

LK3

External Links

Dimming Control

NOTE: Links 2 and 3  
MUST BE 
REMOVED when 
using two dimming 
detectors

PB-A

PB-B

SWA

SWB

N

E

E

Lin

* Note: These specifications relate to the product when used as a simple wiring 
device. When mains-switching presence detectors are used in conjunction with 
this  equipment,  it  is  the  presence  detectors  which  will  normally  dictate  the 
maximum load. It is important to check, and not exceed, the specification of the 
current-switching presence detectors, which will typically be around 6 Amps. 

by Honeywell

Ex-Or

Novar ED&S Limited
Haydock Lane, Haydock, Merseyside WA11 9UJ
Tel: +44 (0)1942 719229  Fax: +44 (0)1942 272767  
Email: [email protected]
www.ex-or.com

Fixing Centres (F) = 340mm
Weight = 1.85 kg