HPS-C - TS operating instructions
Page 26 / 32
Specifications
HPS-C controllers
Operating voltage:
230V / 400V +6/-10%; 50 / 60 Hz
Degree of protection:
IP
33
Output power:
230V: P
Max
= 2500VA per zone or P
Max
= 3500VA per zone
5V:
P
Max
= 625VA per zone (transformer dependent)
Output signal:
230V:
Phase-fired in drying, pulse packet in normal operation
5V:
Phase-fired
Fuse:
- Load circuit: G fuse insert 6.3 x 32 mm; Type A 12 BK (Schurter)
- F 12.5 A (in modules with normal output power)
- F 16 A (in modules with output power 3.5 kW)
- Control circuit: G fuse insert 6.3 x 32 mm, F 6.3 A
Thermocouple input:
Fe-CuNi Type L or J; NiCr-Ni Type K
Signal input 24V:
External decrease, external increase, 2 free inputs
Signal output 24V:
Fault message, warning message, hotrunner ON, 1 free output
Data storage:
EEPROM, data retained at least 10 years
Interface:
CANopen
Ambient conditions:
Working temperature range 0 – 50 °C
Control behaviour:
PID temperature control with adaptive parameter determination and manual
optimization facility
PID
current
control
with
manual optimization facility (5V operation)
Control accuracy:
-
Temperature
control:
±1
°C
-
Current
control:
±1
A
Startup functions:
- Intelligent drying mode for 230V hotrunners
- Setpoint ramps with freely selectable increase
Measurement and
-
Temperature
range: 0
–
500
°C
working ranges:
Sensitivity:
0.1°C
-
Current
5V:
range: 0
–
125
A
Sensitivity:
0.1 A
-
Current
230V:
range: 0
–
16
A
Sensitivity: 0.01
A
Measured value accuracy:
- Temperature: ±3 °C (at 300 °C)
- Current 5V: ±3 A (at 100 A)
Further functions:
- Load error detection interruption, short circuit and partial load-failure
-
Thermocouple-error
detection interruption, short circuit and reverse polarity
- Set value monitoring with 2 tolerance bands for fault and warning messages
-
Decrease
function
-
Increase
function
with
maximum
time
limit
The series HPS-C controllers conform to the standards DIN EN 60204-1 (11/1998), DIN EN 55011 (05/2000), DIN EN
61000-6-2 (03/2000) and DIN EN 61558-1 (07/1998).