background image

Model EWT-3900

Wireless Programmable  Digital Thermostat

Installer :  Save these instructions for future use!

FAILURE TO READ AND FOLLOW INSTRUCTIONS CAREFULLY BEFORE INSTALLATION OR

 OPERATION COULD DAMAGE THIS CONTROL OR CAUSE PROPERTY DAMAGE.

DESCRIPTION

The EWT-3900 7Day/5-2 Day Wireless Programmable 
Digital Solid State Thermostat uses a microcomputer to 
provide precise time and temperature control. This wireless 
thermostat offers additional flexibility to design heating and 
cooling systems where hard wired installations would be 
difficult to do.

Features:

l

 The Thermostat is powered by a rechargeable lithium-ion 

battery. 

l

 The receiver module is powered with 24VAC from a 

Control Panel or 24VAC Class 2 Transformer. 

l

 The receiver module terminal block has the following  

terminals: R, C, W1/E, W2, Y1, Y2, G, O, B and one     
NC (no connection) terminal.

l

 Compatible Equipment:  ULTRA-ZONE Control Panels:                                        

NCM-300, BMPlus3000 & UZC-4.                                
Single or two stage heating and cooling equipment

     Gas, Electric, Oil or Hydronic. One or two stage 

compressor heat pump with electric backup.

l

 Simultaneous heat and cool program storage.

l

 Program storage is retained in case of power loss.

l

 LCD continuously displays time and room temperature. 

Temperature set point is displayed when it is being  
changed.

l

 Temperature display can be configured in °F or °C.

l

 The Thermostat can be programmed between           

45°F and 95°F.

l

 Backlit display.

l

 Air Filter Replacement Monitor.

The Model EWT-3900 Wireless Thermostat is Linked to 
the Receiver at the factory. Simply power up the 
Receiver, then program and operate the Thermostat.

AUTO

FAN

SYSTEM

HEAT

PM

:

1

°

MON

Room

DAY/
TIME

PROG

PROG

DAY

FAN

HOLD

/RUN

MODE

Reviews filter usage 
in hours and minutes 
and also activates
standby mode.

Electrical Ratings

19-30VAC 50/60 Hz 
1.0 Amp (Max load per terminal)

Thermal Ratings 

Set point Temperature Range  45°F to 95°F
Operating Ambient Temperature Range  30°F to 99°F
Storage Temperature Range  14°F to 140°F 
Operating Humidity Range 0-90% R.H. (Non Condensing)

ATTENTION

!

This product does not contain mercury.  However, this 
product may replace a unit which contains mercury.
EWC Controls Inc. would like to advise all technicians 
and consumers that all mercury thermostats should 
be recycled. 

LCD Display:  Shows
 Time, Day, Temperature 
and other system data.

Soft touch Programming
and Function Buttons

Contents:
                 

1 EWT 3900 Thermostat

                 1 EWT 3900 Receiver
                 1 USB Adapter Cord
                 6 Plastic Wall Anchors
                 6 #8 x 1” Screws
                 1 TB-236 Technical Bulletin

Accessories: (not included)
                 

EWT-BC Wall Outlet Charger

                 Replacement Battery
                 Replacement Charging Cord

            

TB-236        090375A0236 Rev. B

TECHNICAL BULLETIN

EWC Controls Inc.   385 Highway 33   Englishtown, NJ 07726   800-446-3110   FAX 732-446-5362     E-Mail- [email protected]

1

Copyright © 2009 EWC Controls All Rights Reserved

Charging Requirements:

                 EWT-BC Wall Outlet Charger
                 PC Computer with USB Port

or

Figure 1

Содержание EWT-3900 Ultra-Zone

Страница 1: ...Thermostat can be programmed between 45 F and 95 F l Backlit display l Air Filter Replacement Monitor The Model EWT 3900 Wireless Thermostat is Linked to the Receiver at the factory Simply power up the Receiver then program and operate the Thermostat AUTO FAN SYSTEM HEAT PM 1 MON Room DAY TIME PROG PROG DAY FAN HOLD RUN MODE Reviews filter usage in hours and minutes and also activates standby mode...

Страница 2: ...han is subject to freezing and or condensation EWC Controls Inc 385 Highway 33 Englishtown NJ 07726 800 446 3110 FAX 732 446 5362 E Mail info ewccontrols com 2 CAUTION To prevent electrical shock and or equipment damage disconnect electric power to HVAC system at main fuse or circuit breaker box until installation is complete WARNING Do not use circuits exceeding specified voltage Higher voltage w...

Страница 3: ...lower Fan Energized on call for Heat and Cool Energized in Cool Mode Energized in Heat Mode Heat Pump 2 2nd Stage Compressor THERMOSTAT TERMINALS CONVENTIONAL SYSTEM C R E W1 W2 Y1 Y2 G O B Single Stage 24 Volt Common 24 Volt hot Heat Mode 1st stage No Output Cool mode 1st stage compressor No output Blower Fan Energized on call for Cool and Heat if HE was selected No Output No Output Multistage 2n...

Страница 4: ... hold the key for five seconds to enter the configuration menu The display will show the first item in the configuration menu The configuration menu table shows the configuration options and an explanation of each option Press the key to step to the next menu item To exit the menu and return to program operation press key If no keys are pressed within fifteen seconds the thermostat will revert bac...

Страница 5: ...et point and the Cool set point can not be set lower than the Heat set point 1 Put Thermostat into RUN MODE in either heat or cool 2 Select program mode either 5 2 day or 7 individual days by pressing key until desired program is selected 3 Press key and in the program window will appear the hour flashing Use the or keys to set the hour Note AM or PM 4 Press key again to change to the minute posit...

Страница 6: ...he heating system should stop operating Copyright 2009 EWC Controls All Rights Reserved FAN FAN MODE Heating System Heatpump Application Only 1 Press the key until HEAT shows on the LCD display 2 Press key to adjust thermostat setting to 2 F 1 C above room temperature The heating system should begin to operate The display should show STG1 However if the set point temperature display begins to flas...

Страница 7: ...revent unauthorized changes from being made To lock or unlock the keyboard press and hold the button for 3 seconds The keyboard is locked when LOCK appears on the display Anytime a key is pressed LOCK will appear on the screen for one second To exit Lock mode press and hold the key for 3 seconds Filter Monitor Your thermostat also keeps a record of the number of days your filter has been in use To...

Страница 8: ...L EWT BC USB CABLE INCLUDED WITH EWT 3900 MODEL EWT 3900 The Model EWT BC is an optional wall charger for the Model EWT 3900 Wireless Thermostat TO USE Attach the USB Cable Provided with the EWT 3900 to the Thermostat and the Charger Then plug the charger into the wall Allow the thermostat to charge for at least 12 hours during the first three charging cycles in order to condition the battery prop...

Страница 9: ...adio or television receiver away from the receiver control Move the antenna leads away from any wire runs to the receiver control Plug the receiver control into a different outlet so that it and the radio or television receiver are on different branch circuits If necessary the user should consult the dealer or an experienced radio television technician for additional suggestions The user or instal...