Model EWT-3707

Programmable Digital Thermostat

Installer :  Save these instructions for future use!

DESCRIPTION

TECHNICAL BULLETIN

The EWT-3707 is a Programmable Digital Solid State 
Thermostat.

Features:

l

 The Thermostat can be powered by 24VAC or two AA 

batteries. If both power sources are used, the batteries 
will backup the 24VAC.

l

 Compatible Equipment:  ULTRA-ZONE Control Panels:                                        

ST-2E/3E, NCM-300, BMPlus3000 & UZC-4.                                
Two Stage Heating and Single Stage Cooling Equipment. 
Gas, Electric, Oil or Hydronic.

l

 LCD continuously displays room temperature. 

Temperature set point is displayed when it is being  
changed.

l

 Temperature display can be configured in °F or °C.

l

 The Thermostat can be programmed between 45°F and 

95°F.

l

 Backlit display.

l

 The thermostat terminal block has the following  

terminals: O, B, L, W2, G, Y1, C, R and E/W1.

l

Filter Monitor to keep track of the systems filter use.

TB-235        090375A0235 Rev. B

EWC Controls Inc.   385 Highway 33   Englishtown, NJ 07726   800-446-3110   FAX 732-446-5362     E-Mail- [email protected]

1

Copyright © 2009 EWC Controls All Rights Reserved

Electrical Ratings

19-30VAC 50/60 Hz 
1.0 Amp (Max load per terminal)

Thermal Ratings 

Set point Temperature Range  45°F to 95°F
Operating Ambient Temperature Range 30°F to 99°F
Storage Temperature Range  14°F to 140°F 
Operating Humidity Range 0-90% R.H. (Non-Condensing)

ATTENTION

!

This product does not contain mercury.  However, this 
product may replace a unit which contains mercury.
EWC Controls Inc. would like to advise all technicians 
and consumers that all mercury thermostats should 
be recycled.  You can take your mercury thermostat 
to your local HVAC wholesaler for recycling.

Contents:
                 

1 EWT-3707 Thermostat

                 2 Plastic Wall Anchors
                 2 #8 x 1” Screws
                 1 TB-235  Technical Bulletin

            

Technical Data

Power

Working Environment

Range

Shell

Dimension

Connection Interface

24VAC, 50/60Hz or two AA
batteries as primary or backup source.

32°F~120°F

5~90%RH(non-condensing)

Fire Retardant PC ABS

3.5x5.1x1.2 in (HxWxD)

Each terminal is capable of accepting

2 x 18 AWG solid copper wires.

WARNING

!

Do not use circuits exceeding specified voltage.  Higher
voltage will damage control and could cause shock or
fire hazard. 

Do not short out terminals on gas valve or primary control
to test.  Shorted or incorrect wiring will damage thermostat
and could cause personal injury and/or property damage.

Thermostat installation and all components of the system
shall conform to Class 2 circuits per the NEC code.

AM

Mon

TEMP

cool

off heat

auto

ON

AUTO

SYSTEM

FAN

HOME

TODAY

ENER

MIN

DAY

PROG

HOLD

/RUN

EMER

PROG

DAY

AUTO

PROG

HOUR

FAILURE TO READ AND FOLLOW INSTRUCTIONS CAREFULLY BEFORE INSTALLATION OR

 OPERATION COULD DAMAGE THIS CONTROL OR CAUSE PROPERTY DAMAGE.

Figure 1

Содержание EWT-3707

Страница 1: ...ature Range 14 F to 140 F Operating Humidity Range 0 90 R H Non Condensing ATTENTION This product does not contain mercury However this product may replace a unit which contains mercury EWC Controls Inc would like to advise all technicians and consumers that all mercury thermostats should be recycled You can take your mercury thermostat to your local HVAC wholesaler for recycling Contents 1 EWT 37...

Страница 2: ...ll components of the system shall conform to Class 2 circuits per the NEC code Copyright 2009 EWC Controls All Rights Reserved Mounting the Thermostat ATTACH THERMOSTAT BASE TO THE WALL Position wallplate on the wall and pull the wires through the large opening Level the unit for appearance Mark the mounting holes for the provided wall anchors Drill holes with a 3 16 bit and gently tap anchors int...

Страница 3: ... exit the menu and return to program operation press key If no keys are pressed within fifteen seconds the thermostat will revert back to program operation HOLD RUN Time Delay The thermostat will provide a 4 minute delay after shutting down the heating or cooling system before it can be restarted if ON is selected at step 8 of the configuration menu This delay applies equally to heating or cooling...

Страница 4: ...inuous Multistage MS2 Heat Mode 2nd stage R W G C COMPRESSOR Y GAS FURNACE E W1 EWT 3707 C R W2 Y1 G L B O E W1 EWT 3707 C R W2 Y1 G L B O E W1 EWT 3707 C R W2 Y1 G L B O Y C R W G C COMPRESSOR Y GAS FURNACE E W1 EWT 3707 C R W2 Y1 G L B O Y C W2 E W1 EWT 3707 C R W2 Y1 G L B O Y R G W E C T T ISOLATION RELAY Non Zoned Hydro 1H 1C Non Zoned Gas or Oil 2H 1C Non Zoned Gas 1H 1C Figure 5 Figure 8 Fi...

Страница 5: ... Reversing Valve Y1 O B W1 E W2 Y2 R G C E W1 EWT 3707 C R W2 Y1 G L B Figure 12 O E W1 EWT 3707 C R W2 Y1 G L B O BmPlus 3000 Y R G O B W E C Heat Pump 2H 1C B Reversing Valve Figure 13 E W1 EWT 3707 C R W2 Y1 G L B O NCM 300 Gas Elec 2H 1C Radiant Baseboard w Hydro Hot Air Figure 10 O G R L C W2 E W1 E W1 EWT 3707 C R W2 Y1 G L B O Y R G W E C T T ISOLATION RELAY O B Non Zoned Heat Pump w Malfun...

Страница 6: ...ng ON OFF at Step 2 of the installer configuration menu Auto Recovery will not operate if Permanent Hold or Temporary Hold is in operation Auto Programming Studies conducted by the Department of Energy estimates that setting your thermostat back 10 F 6 C for two 8 hour periods during the winter can reduce your fuel bill by as much as 33 By setting your thermostat up to 5 F 3 C for 2 8 hour periods...

Страница 7: ...ut Thermostat into RUN MODE in either heat or cool depending on what mode you would like to operate 2 Select program mode 5 2 day by pressing key until Saturday and Sunday is displayed on the screen 3 Press key and the program window will appear 4 Use the key to set the hour Note AM or PM 4 Press key to change to the minute position The minutes will change in increments of 15 5 Use the or keys to ...

Страница 8: ...set temperature Press either or again to change your desired set point temperature Hold the key down for over 2 seconds to fast advance the set point temperature Auto Shut Off Your thermostat will automatically cut off in HEAT mode if the room temperature rises above 95 F 35 C It will cut off in COOL mode if the room temperature drops below 45 F 7 C Note that if your system has malfunctioned and n...

Отзывы: