The following table shows and explains all possible error
messages which can be displayed. If several errors occur at the
same time, the corresponding messages appear alternately in
succession. When the error has been remedied, the error
message is automatically deleted.
If you are unable to remedy the error yourself, please contact your
contractual partner.
Error message
Cause
Remedy
Measured value
display flashes
Measured value is outside the
measuring range
Check measuring range and change, if
necessary. Check dosing or controller
settings
Positioner feedback
flashes
Positioner in manual mode
Press the adjusting nob on the
positioner
DI I flashes
Sample water flow recently
insufficient (delay running)
Check sample water flow rate
(approx. 33 l/h)
DI I Permanent
display
Sample water flow insufficient for
some time (delay elapsed)
Clean or replace the preliminary filter
Multi-sensor incorrectly connected
or defective
DI II and DI III
Signal on signal input DI II or DI III
Check connection and setting
Zero Mod1
Zero Mod2
Zero Mod3
Zero Mod4
In 3 electrode cells
Sensor has zero current > +5 µA or
< -5 µA
Upot potential voltage set incorrectly;
change, if necessary
Electrodes in the 3 electrode cell are
soiled; clean and service, if necessary
Sample water is not turned off or check
valve leaks; turn off sample water, if
necessary
In membrane sensors
Sensor has zero current > +5 µA or
< -5 µA
Disinfectant in water; calibrate with
disinfectant-free water, if necessary
Check sensors and replace or service,
if necessary
Содержание WALLACE & TIERNAN MFC
Страница 1: ...WALLACE TIERNAN MULTI FUNCTION CONTROLLER MFC from version V 2 00 INSTRUCTION MANUAL...
Страница 2: ...2 WT 050 580 000 DE IM 0714 MFC Please note Original manual...
Страница 6: ...6 WT 050 580 000 DE IM 0714 Introduction MFC 1...
Страница 40: ...40 WT 050 580 000 DE IM 0714 Description MFC 3...
Страница 225: ...MFC Complete Devices Retrofit Kits and Spare Parts 8 225 DEPOLOX 5 drawing non pressurised version W3T170031 W3T170031...
Страница 229: ...MFC Complete Devices Retrofit Kits and Spare Parts 8 229 DEPOLOX 5 drawing pressurised version W3T170032 W3T170032...
Страница 233: ...MFC Complete Devices Retrofit Kits and Spare Parts 8 233 VariaSens drawing non pressurised version W3T158742 W3T158742...
Страница 237: ...MFC Complete Devices Retrofit Kits and Spare Parts 8 237 VariaSens drawing pressurised version W3T158756 W3T158756...
Страница 247: ...MFC Certificates 10 247 10 Certificates...
Страница 248: ...248 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Страница 249: ...MFC Certificates 10 249...
Страница 250: ...250 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Страница 262: ...262 WT 050 580 000 DE IM 0714 Settings table MFC 11...
Страница 266: ...266 WT 050 580 000 DE IM 0714 Index MFC 12...