MFC
Operation
5.
143
Module designation
Module 1 to 4
Max. 6 digits, customised entry
If blanks are entered, the module
description is switched off.
System reset
System restart
4)
yes / no
Delete graph
5)
yes / no
Standard value
6)
yes / no
Delete dos. avg
7)
yes / no
Dosing Factors
8)
0–100 %
Please note
The system settings marked with 1) to 8) are explained below.
Explanation of system settings
1)
Measure Filter
The dampening serves to compensate measurement value
fluctuations in the event of irregular measurement value signals.
2)
Feed delay
The feed delay delays dosing start when the device is switched on
and when the operating mode has been changed. Running of the
selected time can be cancelled with the "Acknowledge" key.
3)
Samp.water delay
The sample water delay (DI 1) determines the time after which
dosing is deactivated, e.g. in the event of sample water stop. DI 1
flashes while the delay time is running.
4)
System restart
When the applications are changed, the device must be restarted
with System Restart.
5)
Delete graph
Deletes the values saved in the past 7 days.
6)
Standard values
Deletes customer settings (except for the selected application),
resets system to factory settings. The sensors must be
recalibrated.
7)
Delete dos.avg
Resets the average dosing values from display 1.8.3 to zero.
8)
Dosing Factors
Resets the dosing factor table to the set value and all training
meters to zero.
Содержание WALLACE & TIERNAN MFC
Страница 1: ...WALLACE TIERNAN MULTI FUNCTION CONTROLLER MFC from version V 2 00 INSTRUCTION MANUAL...
Страница 2: ...2 WT 050 580 000 DE IM 0714 MFC Please note Original manual...
Страница 6: ...6 WT 050 580 000 DE IM 0714 Introduction MFC 1...
Страница 40: ...40 WT 050 580 000 DE IM 0714 Description MFC 3...
Страница 225: ...MFC Complete Devices Retrofit Kits and Spare Parts 8 225 DEPOLOX 5 drawing non pressurised version W3T170031 W3T170031...
Страница 229: ...MFC Complete Devices Retrofit Kits and Spare Parts 8 229 DEPOLOX 5 drawing pressurised version W3T170032 W3T170032...
Страница 233: ...MFC Complete Devices Retrofit Kits and Spare Parts 8 233 VariaSens drawing non pressurised version W3T158742 W3T158742...
Страница 237: ...MFC Complete Devices Retrofit Kits and Spare Parts 8 237 VariaSens drawing pressurised version W3T158756 W3T158756...
Страница 247: ...MFC Certificates 10 247 10 Certificates...
Страница 248: ...248 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Страница 249: ...MFC Certificates 10 249...
Страница 250: ...250 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Страница 262: ...262 WT 050 580 000 DE IM 0714 Settings table MFC 11...
Страница 266: ...266 WT 050 580 000 DE IM 0714 Index MFC 12...