Troubleshooting Guide
Component
Problem
Probable Cause
Solution
Vacuum
Transfer
System
Vacuum does not
turn on when
activated on control
panel.
Vacuum unit is not
turned on at the device.
Toggle on/off switch while vacuum is
active on control panel.
Vacuum is not getting
power.
Verify wiring is correct and power is
present at the control panel.
No suction at hose
end while vacuum is
running.
Vacuum hose or port is
clogged.
Disconnect hose and ensure there is no
blockage in the hose or port.
Vacuum filter is clogged
or full of water.
Inspect vacuum canister and ensure
everything is clean.
Valves are not
configured properly.
Verify that ball valves are in the correct
orientation.
Ensure the precoat and effluent valves
are closed.
Valves with
Pneumatic
Actuators
Actuator is not
operating.
No air is getting to or
from the actuator.
Check system air pressure. Confirm at
80-90 PSI.
Check air line tubing is properly
attached.
Check for leaks in the air lines and
fittings.
Air flow is restricted due
to needle valves being
closed.
Confirm the needle valves are open to
allow air flow and are properly adjusted.
Actuator is moving
too quickly or slowly.
Air flow needs to be
adjusted at the needle
valves on the actuator.
Turn knobs counterclockwise to
increase actuator speed. Turn knobs
clockwise to decrease actuator speed.
Valve disk is sticking
closed and then
slamming open.
Valve stops are out of
adjustment.
Adjust the actuator limit stops so that
the valve closes, but does not stick
closed.
No air is getting to the
actuator.
Check system air pressure. Confirm at
80-90 PSI.
Check air line tubing is properly
attached.
Check for leaks in the air lines and
fittings.
Precoat valve did
not open or close
when it was
supposed to.
No air is getting to the
actuator.
Inspect pneumatic solenoid operation.
Effluent valve did
not open or close
when it was
supposed to.
No air is getting to the
actuator.
Inspect pneumatic solenoid operation.
Содержание DEFENDER SP-27-48-487
Страница 14: ...Page 14 General Installation Schematic ...
Страница 15: ...Page 15 DIMENSIONAL REFERENCE Standard Defender ...
Страница 16: ...Page 16 Assero Defender Reduced Height Defender ...
Страница 17: ...Page 17 Reduced Height Defender ...
Страница 72: ...Page 72 Figure 33 Alarm History Screen CLEAR HISTORY Clears all alarm and warning messages from the system ...
Страница 77: ...Page 77 APPENDIX ...
Страница 78: ...Page 78 Electrical Schematic ...
Страница 79: ...Page 79 Head Loss Curve ...