1. FOREWORD
1.1. Read the Manual Before Operation
WARNING
Do not use means to accelerate the defrosting process or to clean, other than those
recommended by the manufacturer. The appliance shall be stored in a room without continuously
operating ignition sources (for example: open flames, an operating gas appliance or an operating
electric heater).
Do not pierce or burn.
Be aware that refrigerants may not contain an odour.
Initial safety checks shall include:
①
That capacitors are discharged: this shall be done in a safe manner to avoid possibility of
sparking;
②
That no live electrical components and wiring are exposed while charging, recovering or
purging the system;
③
That there is continuity of earth bonding.
Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety checks are
necessary to ensure that the risk of ignition is minimized. For repair to the refrigerating system,
the following precautions shall be completed prior to conducting work on the system.
Work procedure
Work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable
gas or vapour being present while the work is being performed.
General work area
All maintenance staff and others working in the local area shall be instructed on the nature of
work being carried out. Work in confined spaces shall be avoided.
Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work, to
ensure the technician is aware of potentially flammable atmospheres. Ensure that the leak
detection equipment being used is suitable for use with flammable refrigerants, i.e. non-sparking,
adequately sealed or intrinsically safe.
Presence of fire extinguisher
If any hot work is to be conducted on the refrigerating equipment or any associated parts,
appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO2
fire extinguisher adjacent to the charging area.
No ignition sources
No person carrying out work in relation to a refrigeration system which involves exposing any
pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in
such a manner that it may lead to the risk of fire or explosion. All possible ignition sources,
including cigarette smoking, should be kept sufficiently far away from the site of installation,
repairing, removing and disposal, during which flammable refrigerant can possibly be released to
the surrounding space. Prior to work taking place, the area around the equipment is to be
surveyed to make sure that there are no flammable hazards or ignition risks. “No Smoking” signs
shall be displayed.
Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into the
system or conducting any hot work. A degree of ventilation shall continue during the period that
the work is carried out. The ventilation should safely disperse any released refrigerant and
Содержание evotherm EFI Ultra V30T
Страница 16: ...13 ...
Страница 18: ...15 ...
Страница 32: ...29 2 Account ID Password Login Existing accounts can be logged in directly in the following order ...
Страница 36: ...33 Step 5 When Scan devices Register on Cloud Initialize the device are all completed connect succeeds ...
Страница 42: ...39 Mode settings Click on the main interface to switch modes select what you need Timer setting ...
Страница 45: ...42 ...
Страница 47: ......
Страница 48: ......