The EVO/

TM

IRC-Remote is a handheld infrared remote control configured to 

adjust a General Electric ECM Motor Controller.  
 
An EVO/

TM

ECM-IRC control sends the ECM motor a FLOW INDEX and a GO 

signal.  The motor sends back a status signal that is connected to a 

red lamp

.  

The control includes an infrared remote receiver. 
 
The handheld remote sends infrared remote commands to the EVO/

TM

ECM-IRC 

control, allowing remote adjustment of the ECM motor.  Using the remote, you 
can turn the motor on/off, adjust the flow index from 1-100 and read the current 
settings. 
 
Point the remote at the target (

red lamp

 if the motor is on) on the equipment. 

Operate the on/off button or any of the four 

/

 buttons.   The 

green lamp

 near 

the target lights, indicating you are in an adjustment session.  Continue to 
operate the on/off button or any of the four 

/

 buttons to achieve the desired 

settings.  Press the Enter button to save your new settings and exit the 
adjustment session.  Press the Clear button to delete your new settings, revert to 
the original settings and exit the adjustment session.  If you enter an adjustment 
session and do not make any adjustments for 15 minutes, the adjustment 
session automatically clears. 
 
Use the Clear button to read the current settings. Point the remote at the target 
and press the Clear button.  A 

green lamp

 begins to flash indicating the signal 

was received.  The flash sequence indicates the current flow index.  The 
sequence occurs in two sets.  The tens (1

st

) set uses long flashes to indicate the 

tens digit.  The units (2

nd

) set uses short flashes to indicate the units digit.  An 

extra long flash in the tens set or the units set indicates the value of the 
corresponding digit is zero.   
 

 

A flow index of 24 flashes two longs, then 4 shorts.   

 

 

A flow index of 89 flashes 8 longs, then 9 shorts. 

 

 

A flow index of 30 flashes 3 longs, then an extra long. 

 

 

A flow index of 04 flashes an extra long, then 4 shorts. 

 

 

A flow index of 100 flashes 10 longs, then an extra long. 

 
 