Содержание Solace Universal C-1200

Страница 1: ...P a g e 1...

Страница 2: ...14 6 Start up Check List 14 6 1 Pre Start Checklist 14 6 2 Start Up 15 7 Operation 16 7 1 How to Control 16 7 2 Run Mode Menu 17 7 3 Alarms Menu 20 7 4 Sensors Off Set Menu 20 7 5 Run state Menu 21 7...

Страница 3: ...ion is satisfied SPACE HEATING When the compressor is running space heating will continue until the space temperature reaches the set point The controller will activate the auxiliary space heating sys...

Страница 4: ...or This hot gas refrigerant then travels either through an air reheat coil the pool water condenser or to an optional auxiliary air conditioning condenser which may be either air or water cooled If ai...

Страница 5: ...erated in an abnormal condition it may cause a fire or hazards Apply Grounding Do not connect a grounding wire to a gas pipe water pipe lightning rod or ground wire of a telephone If a grounding is in...

Страница 6: ...ric shock water leakage etc Ensure that you consult your dealer Do not apply an insecticide or flammable spray It may cause a fire or deformation of the cabinet Do not clean the unit with water Water...

Страница 7: ...P a g e 7 4 Installation 4 1 Installation Diagram...

Страница 8: ...ace where the exterior of the unit would be exposed to chloramines outgassing from a pool d Ensure that water cannot collect under the unit it is recommended that units are installed on plinths 100mm...

Страница 9: ...P a g e 9 4 3 Ducts Installation...

Страница 10: ...g see data sheet H R C Fuses are recommended An isolator must be fitted within clear view of the machine and not more than 2 meters away The isolator must have a minimum of 3mm air gap when in the off...

Страница 11: ...n the boiler water flow and return pipes local to the dehumidification unit Refer to the boiler manufacturer s instructions before designing the pipework system IMPORTANT GENERAL CONDITIONS 1 Do not r...

Страница 12: ...taken to see that ample room is left for maintenance work through access doors and panels Overhead obstructions are not permitted When the unit is in an area where it is enclosed by three walls the un...

Страница 13: ...and a sealing material around refrigerant lines where they penetrate a wall to reduce vibration and to retain some flexibility The liquid line and discharge line should not be in contact with one anot...

Страница 14: ...p Check List 6 1Pre Start Checklist Before starting the unit be sure that the following items have been completed Ensure there is enough space to install the unit See Installation for installation rec...

Страница 15: ...3 Disconnect power from the dehumidifier unit Re tension the blower belt Turn on the pool water supply to the unit Use valves in the water line to set the flow rate to the range called out on the unit...

Страница 16: ...rmance data of Air Cooling 10 If the unit is equipped with an auxiliary air conditioning condenser change the water temperature set point lower higher than current air temperature This should cause th...

Страница 17: ...ification and water heating dehumidification and air cooling The above screen contains basic information of the status and target set point status displays Space Temp Room space temperature in Space H...

Страница 18: ...ns basic information of the status and the selective running mode There are three options to choose Manual Humidity Off On Ventilation Only Off On Manual Fresh Air Off On There are three different run...

Страница 19: ...idDiff The humidity difference of room space relative humidity in PoolTempDiff The temperature difference of pool water temperature in AuxAirHeatDif The temperature difference for auxiliary air space...

Страница 20: ...ing by an experienced HVAC technician The dehumidifier may stop when the fault occurs Press the reset button after the fault has been eliminated to go back to normal operation 7 4 Sensors Off Set Menu...

Страница 21: ...5 Run state Menu The RUNSTATE screen contains the technical information of the status the dehumidifier 7 6 Curves Menu The CURVES screen is to display the value of Room Space temperature and Room Spa...

Страница 22: ...er unit has numerous safety devices designed to protect the system from failures Whenever a fault condition occurs the alarm message will display on the screen The dehumidifier may stop when the fault...

Страница 23: ...ct obstruction Expansion valve problem Replace expansion valve 2 Compressor high pressure protection A C condenser power off Restore power to A C Only the faulty system stops A C condenser fan gets bl...

Страница 24: ...tor Only the faulty system stops Obstruction in return duct system Remove duct obstruction Expansion valve problem Replace expansion valve 4 Compressor high pressure protection A C condenser power off...

Страница 25: ...P a g e 25 9 Circuit Diagram C 1200 C 1500 THREE PHASE 3 N 50Hz...

Страница 26: ...P a g e 26 10Dimension and Parts 10 1 Description of Parts and Dimensions Dehumidifier Indoor Unit...

Страница 27: ...P a g e 27 Air Cooled Condenser Outdoor Unit...

Страница 28: ...ensate is not overflowing Check the condensate and overflow lines to ensure that neither are clogged C Check the operation of the blower motor and compressor Ensure that the compressor does not rub th...

Страница 29: ...nt Type R407c Protections Type Phase Protection High Low Pressure Protection Overload Protection Water Proof PCB Compressor staged start Compressor Auto Protection Fan Motor Auto Protection Condenser...

Страница 30: ...ealer s information You also need to record the model name and serial number You can find this information from your dehumidifier or ask your dealer Model number ______________________________________...